10
8.2 Configuration of the switching outputs
Factory setting 1 x normally closed (S1); 1 x normally open (S2)�
Reversion of the programming:
►
Press the pushbutton
for at least 15 s�
> LED 0 lights, after approx� 5 s it flashes�
> After 10 s the current setting is displayed: LEDs 5���9 light orange�
> After approx� 15 s LEDs 0���4 flash orange�
►
Release the button�
> The outputs are set to 1 x normally open (S1); 1 x normally closed (S2)�
For a new changeover: repeat the operation�
8.3 Restore the factory setting (reset)
►
Press for at least 15 s�
> LED 9 lights, after approx� 5 s it flashes�
> After approx� 15 s LEDs 0���9 flash orange�
►
Release the button� All settings are reset to the factory setting�
8.4 Lock / unlock the unit
The unit can be locked electronically to prevent unintentional settings�
►
Press both setting buttons simultaneously for 10 s in the operating mode�
> The indication goes out, the unit locks or unlocks�
On delivery: unlocked�