11.3 Read set parameters
► Press [Mode/Enter] until the requested parameter is displayed�
► Briefly press [Set]�
> The unit displays the corresponding parameter value�
> After about 15 s (from menu level 1) or 30 s (from menu level 2) it again dis-
plays the parameter, then it returns to the Run mode�
11.4 Fault indications
[SC1]
Short circuit in OUT1*
[SC2]
Short circuit in OUT2*
[SC]
Short circuit in both outputs*
[OL]
Measured value > 120 % of the final value of the measuring range
[UL]
Measured value < -20 % of the final value of the measuring range (temperature)
[Err]
Flashing: error in the measuring probe or measured value > 130 % of the final
value of the measuring range
*The output concerned is switched off as long as the short circuit exists�
These messages are displayed even if the display is switched off�
11.5 General operating conditions
The unit is maintenance-free for media which do not stick to the measuring
probes�
• From time to time check the measuring probes visually for build-up�
• If necessary, clean them at regular intervals� To do so, use a suitable cleaning
liquid (e�g� alcoholic solution)�
• Avoid mechanical damage to the measuring probes�