For the scope of validity cULus: The device shall be supplied from an isolating 

transformer having a secondary Listed fuse rated as noted in the following table�

Overcurrent protection

Control-circuit wire size

Maximum protective device rating 

Ampere

AWG

(mm

2

)

26

(0�13)

1

24

(0�20)

2

22

(0�32)

3

20

(0�52)

5

18

(0�82)

7

16

(1�3)

10

3  Functions and features

The unit monitors the standard volume flow of operating compressed air�

It detects the 3 process categories volumetric flow, consumed quantity, medium 

temperature�
Applications: compressed air equipment�

All data refer to standard volume flow according to DIN ISO 2533, i�e� volume flow 

at 1013 hPa, 15°C and 0 % relative air humidity�

The general operating conditions of compressed air equipment apply�

Pressure Equipment Directive (PED): Devices with a measuring section comply 

with art� 3 sec� (3) of the Directive 97/23/EC and are designed and manufac-

tured for stable gases of the fluid group 2 in accordance with sound engineering 

practice�

4  Function

4.1  Processing of the measured signals

•  The unit displays the current process values�

•  It generates 2 output signals according to the parameter setting�

OUT1: 3 selection options �����������������������������������������������������  parameter setting

switching signal for volumetric flow limit values  ���������������������������������� (→ 9.2.1)

or pulse sequence for totalising meter  ������������������������������������������������ (→ 9.3.1)

or switching signal for preset counter  ������������������������������������������������� (→ 9.3.2)
OUT2: 2 selection options

switching signal for volumetric flow limit value  ����������������������������������� (→ 9.2.2)

or analogue signal for volumetric flow  ������������������������������������������������ (→ 9.2.3)

Содержание efector300 SD6001

Страница 1: ...Operating instructions Compressed air meter SD6001 80004719 00 10 2013 UK ...

Страница 2: ...allation 8 5 1 Installation location 8 5 2 Installation conditions 9 5 3 Mounting position 10 5 4 Installation in pipes 11 6 Electrical connection 11 7 Operating and display elements 12 8 Menu 13 8 1 Menu structure 13 8 2 Explanation of the menu 14 9 Parameter setting 15 9 1 General parameter setting 15 9 2 Settings for volumetric flow monitoring 16 9 2 1 Settings for limit value monitoring with O...

Страница 3: ...the measured values 18 9 4 4 Setting the error behaviour of OUT1 OUT2 18 9 5 Service Funktionen 19 9 5 1 Reading the min max values for volumetric flow 19 9 5 2 Reset all parameters to the factory setting 19 9 6 Setting of the preset meter pulse value ImPS 20 10 Operation 22 10 1 Read the set parameters 22 10 2 Changing the display unit in the Run mode 22 10 3 Error indication 22 10 4 General oper...

Страница 4: ...compressed air equipment Improper or non intended use may lead to malfunctions of the unit or to unwanted effects in your application That is why installation electrical con nection set up operation and maintenance of the unit must be carried out by qualified personnel authorised by the plant operator In all applications test the compatibility of the product materials 11 Technical data and scale d...

Страница 5: ...low at 1013 hPa 15 C and 0 relative air humidity The general operating conditions of compressed air equipment apply Pressure Equipment Directive PED Devices with a measuring section comply with art 3 sec 3 of the Directive 97 23 EC and are designed and manufac tured for stable gases of the fluid group 2 in accordance with sound engineering practice 4 Function 4 1 Processing of the measured signals...

Страница 6: ...this value is available as the current meter count If a time controlled reset is set the elapsed time of the set reset interval is also stored So the possible data loss can be maximum 10 minutes The meter can be reset as follows Manual reset 9 3 3 Time controlled automatic reset 9 3 3 4 3 1 Consumed quantity monitoring with pulse output Output 1 provides a counting pulse if the value set in ImPS i...

Страница 7: ...1 OUx Hno Hysteresis function normally closed fig 1 OUx Hnc First the set point SPx is set then the reset point rPx at the requested distance Window function normally open fig 2 OUx Fno Window function normally closed fig 2 OUx Fnc The width of the window can be set by means of the distance between SPx and rPx SPx maximum value rPx minimum value 1 2 HY hysteresis FE window When set to the window f...

Страница 8: ... the output signal is between 4 and 20 mA It is also indicated Volumetric flow above the measuring range output signal 20 mA Flow rate below the measuring range output signal between 3 6 and 4 mA 5 Installation The rules and regulations for the installation and operation of compressed air equipment must be observed 5 1 Installation location Behind the cold dryer near the load If compressed air is ...

Страница 9: ...ion depth and correct positioning of the measuring elements The unit is delivered mounted on a pipe section meeting these conditions In case of turbulances at the inflow side additional baffled pipes B are recom mended changes to the pipe diameter B 5 x pipe diameter 90 elbow B 5 x pipe diameter two 90 elbows one plane B 10 x pipe diameter two 90 elbows two planes B 15 x pipe diameter valve slide ...

Страница 10: ...ical any position fig 1 2 pipe length horizontal unit vertical fig 3 5 unit on side pipe length left fig 4 Avoid the mounting position shown in fig 6 unit on side pipe length right If the flow rate is low the specified measurement accuracy cannot be adhered to 1 2 3 4 5 6 ...

Страница 11: ...l regulations for the installation of electrical equipment must be adhered to Voltage supply to EN 50178 SELV PELV Disconnect power Connect the unit as follows 2 switching outputs 1 switching output 1 analog output L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 L L 3 4 2 1 BU BK WH BN 2 OUT2 4 OUT1 OUT1 switching signal or pulse sequence pnp OUT2 switching signal pnp or analogue signal I Core colours of if...

Страница 12: ...3 and 5 flashing consumed quantity before the last reset in 103 standard cubic feet LED 4 current medium temperature in F LED 6 not used LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 digits Indication of the current volumetric flow if SELd FLOW is set indication of the meter count if SELd TOTL is set indication of the current medium temperature 10 2 indication of...

Страница 13: ...13 UK 8 Menu 8 1 Menu structure Mode Enter Set scf current meter count in standard cubic feet scf stored meter count in standard cubic feet ...

Страница 14: ... Analogue signal 4 20 mA SP2 rP2 Maximum minimum value for volumetric flow at which OUT2 changes its switching status ASP Analogue start value for volumetric flow AEP Analogue end value for volumetric flow EF Extended functions opening of menu level 2 HI LO Maximum minimum value memory for volumetric flow FOU1 Behaviour of output 1 in case of an internal fault FOU2 Behaviour of output 2 in case of...

Страница 15: ...m eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduced let the display move to the maximum setting value Then the cycle starts again at the minimum setting value 3 Acknowledgement of the parameter value Press Mode Enter briefly The parameter is display...

Страница 16: ...alues Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Time out If during parameter setting no pushbutton is pressed for 15 s the unit exits the param eter setting mode The parameter value is not changed 9 2 Settings for volumetric flow monitoring 9 2 1 Settings for limit value monitoring with OUT1 Select OU1 and set the switching function Hno hysteresis function normally op...

Страница 17: ...for quantity monitoring by pulse output Select OU1 and set ImP Select ImPS and set the volumetric flow quantity at which 1 pulse is provided 9 6 Select ImPR and set YES Pulse repetition is active Output 1 provides a counting pulse when the value set in ImPS is reached 9 3 2 Settings for quantity monitoring using the preset meter Select OU1 and set ImP Select ImPS and set the volumetric flow quanti...

Страница 18: ...he update rate and orientation of the display d1 update of the measured values every 50 ms d2 update of the measured values every 200 ms d3 update of the measured values every 600 ms rd1 rd2 rd3 display as for d1 d2 d3 rotated by 180 OFF the display is switched off in the operating mode 9 4 3 Setting the damping of the measured values Select dAP and the damping constant in seconds t value 63 9 4 4...

Страница 19: ...ode Enter briefly It makes sense to delete the memories as soon as the unit works under normal operating conditions for the first time 9 5 2 Reset all parameters to the factory setting Select rES then press Set and keep it pressed until is dis played Press Mode Enter briefly The factory setting is listed at the end of the instructions 12 Factory setting It makes sense to write your own settings in...

Страница 20: ... 000 000 scf Setting operation Ensure that OU1 is set to ImP Select ImPS press Set and keep it pressed The current numerical value flashes for 5 s then one of the 4 digits becomes active digit flashes can be changed Set the requested value as indicated in the following table First select the requested setting range Then set the figure from the left digit to the right digit Press Mode Enter briefly...

Страница 21: ...urth digit flashes unchanged for 3 s digit 1 becomes active again if the value of digit 1 is 0 8 1 2 3 no pushbutton pressed after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 If digit 1 has the value 0 the display changes to the next lower setting range 0 1 2 3 no pushbutton pressed after 3 s 0 1 2 3 after 3 s 0 1 2 3 after 3 s 0 1 2 3 after 3 s new digit 4 active and set to ...

Страница 22: ... the output signal is at the maxi mum value during the power on delay time 10 1 Read the set parameters Press Mode Enter until the requested parameter is displayed Press Set briefly The unit displays the corresponding parameter value for about 15 s After another 15 s the parameter is displayed again then the unit returns to the Run mode 10 2 Changing the display unit in the Run mode Press Set brie...

Страница 23: ... a suitable cleaning liquid e g alcoholic solution Avoid mechanical damage to the measuring probes 11 Technical data and scale drawing Technical data and scale drawing at www ifm com Data sheet search Enter the article number 12 Factory setting Factory setting User setting SP1 540 rP1 525 ImPS 0 040 ImPR YES OU1 Hno OU2 Hno SP2 1080 rP2 1065 ASP 0 AEP 2650 FOU1 OFF FOU2 OFF dAP 0 6 rTo OFF diS d3 ...