14
10 Operation
After power on, the unit is in the Run mode (= normal operating mode)� It carries
out its measurement and evaluation functions and provides output signals accor-
ding to the set parameters�
Operating indications → chapter 7 Operating and display elements.
10.1 Reading of the set parameters
► Press [Mode/Enter] until the requested parameter is displayed�
► Press [Set] briefly�
> The unit displays the corresponding parameter value for about 15 s� After
another 15 s the unit returns to the Run mode�
10.2 Fault indication
[OL]
Overload pressure (measuring range exceeded)
[UL]
Underload pressure (below measuring range)
[SC1]
Short circuit in OUT1*
[SC2]
Short circuit in OUT2*
[SC]
Short circuit in both outputs*
[Err]
Flashing: internal fault
*The output concerned is switched off as long as the short circuit exists�
The messages SC1, SC2, SC, and Err are shown even if the display is switched off�