Bedienungsanleitung

Operating instructions

Notice utilisateurs

Elektronischer

Drucksensor

Electronic pressure

sensor

Capteur de pression

électronique

PL2058

R

DEUTSCH

ENGLISH

FRANÇAIS

Sachnr

. 701712/00     08/02

Содержание Efector 500 PL2058

Страница 1: ...dienungsanleitung Operating instructions Notice utilisateurs Elektronischer Drucksensor Electronic pressure sensor Capteur de pression électronique PL2058 R DEUTSCH ENGLISH FRANÇAIS Sachnr 701712 00 08 02 ...

Страница 2: ... Functioning Parameters page 19 3 Programming Use with EPS interface page 17 2 Use with factory setting page 14 Safety instructions Please read the product description prior to installing the unit Please check that the product is suitable for your application without any restrictions If the operating instructions or the technical data are not adhered to personal injury and or damage to property ma...

Страница 3: ...x 3 2 mA depending on the scaling Applications Avoid static and dynamic overpressure exceeding the given over load pressure Even if the bursting pressure is exceeded only for a short time the unit can be destroyed danger of injuries The unit is ready for operation when delivered Factory preset not scaled 13 1 Function and features ENGLISH Bursting pressure Permissible overl pressure Measuring rang...

Страница 4: ...amping flange or similar B If it is not possible to slide the fix ing element B down over the top of the sensor slide it up over the bottom of the sensor before the adapter is mounted Note Sensor and adapter are only to be mounted once Mounting of the adapter Step 1 Grease thread and sealing cham fer of the sensor and of the adapter with the greasing paste supplied The greasing paste is food grade...

Страница 5: ...aling Electrical connection The unit must only be connected by an electrician The national and international regulations for the installation of electrical equipment must be observed Voltage supply to EN50178 SELV PELV Disconnect power before connecting the unit Wiring 15 2 ENGLISH Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black n c not connected L 3 4 2 1 BU BK BN WH L n c ...

Страница 6: ...pliers with plastic covered jaws for this Clean the cover thoroughly The vent A should only be cleaned by skilled personnel and with utmost care Possible medium residues must not be compressed and pressed into the vent This could clog the filter system and reduce the measuring accuracy of the sensor Screw the filter cover again tightly The sensor is sufficiently protected against harsh ambient con...

Страница 7: ...luation Output of the current analog value Programming remote programming of the sensor Scaling the measuring range damping for the analog output cali bration of the sensor Parameters can be set before the sensor is mounted and set up or during operation If you change the parameters during operation the functioning of the plant will be affected Ensure that plant malfunction is prevented 17 3 ENGLI...

Страница 8: ...nect power before connecting the unit Do not disconnect these connections while live Programming A service program for the PC which is easy to use and self explanatory order no E30069 is available for the programming of the sensor 18 3 Programming Use with EPS RS232 interface Core colours of ifm sockets 1 BN brown 2 WH white 3 BU blue 4 BK black n c not connected RS232 2 3 Rx Tx GND 2 5 1 2 3 4 L ...

Страница 9: ...easured pressure LO displays the lowest measured pressure Damping for the analog output Pressure peaks of short duration or high frequency can be filtered out dAA value response time between pressure change and change of the switching status in milliseconds ms setting range 0 dAA is not active 0 1s 0 5s 2s Display unit The measured values and values for ASP AEP can be indicated in the following un...

Страница 10: ... temperature fluctuations 10K 0 1 Long time stability in of the span per year 0 1 Temperature coefficients TEMPCO in the compensated temperature range 0 80 C in of the span per 10 K greatest TEMPCO of the zero point 0 1 greatest TEMPCO of the span 0 4 Operating temperature C 25 80 Medium temperature C 25 80 Protection IP 67 III Insulation resistance MΩ 100 500 V DC Shock resistance g 50 DIN IEC 68...

Страница 11: ...tance between ASP and AEP 25 of the span scal ing factor 4 The output signal is between 4 and 20 mA in the set measuring range It is also indicated System pressure above the measuring range output signal 20 mA System pressure below the measuring range output signal drops to max 3 2 mA depending on the scaling 21 ENGLISH 4 Technical information Functioning Parameters I mA P 4 20 MEW 0 1 I mA P 4 20...

Страница 12: ...3 V x 50 550 at Ub 24 V Permissible overl pressure mbar 10000 Bursting pressure mbar 30000 Factory setting ASP 0 mbar AEP 250 mbar COF 0 0 dAA 0 Uni mbar Setting range Analog output lower end ASP mbar Analog output upper end AEP mbar in steps of mbar 12 5 100 0 50 0 250 0 0 5 Accuracy deviations in of the span Turn down 1 1 Characteristics deviation Linearity Hysteresis Repeatability Long time sta...

Страница 13: ...0 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV IEC 1000 4 6 HF conducted 10 V Housing material stainless steel 316S12 PEI FPM Viton Materials wetted parts stainless steel 316S12 ceramics 99 9 Al2 O3 PTFE Connection M12 connector Wiring Remarks linearity incl hysteresis and repeatability limit value setting to DIN 16086 with temperature fluctuations 10 K in of the span per year efector inc 805 Sp...