23
US
9.5.5 Calibration reset
►
[Select [CAr]�
►
Press [Set] and keep it pressed until [----] is displayed�
►
Press [Mode/Enter] briefly�
> Value is reset (CGA = 100)�
9.5.6 Setting the start-up delay
►
Select [dSt] and set the numerical value in seconds�
9.5.7 Setting the damping of the measured values
►
Select [dAP] and the damping constant in seconds (t value 63 %)�
9.5.8 Setting the error behaviour of OUT1 / OUT2
►
Select [FOU1] and determine the value:
[On] = output 1 switches ON in case of an error�
[OFF] = output 1 switches OFF in case of an error�
►
Select [FOU2] and determine the value:
[On] = output 2 switches ON in case of an error, the analogue signal
goes to the upper end stop value�
[OFF] = output 2 switches OFF in case of an error, the analogue signal
goes to the lower end stop value�
9.5.9 Selection of the medium to be monitored
►
Select [MEDI] and determine the required medium:
-[H2O] = Water�
-[GLYC] = Glycol solutions�
-[OIL] = Oils�
9.6 Service-Funktionen
9.6.1 Reading the min./max. values for volumetric flow
►
Select [HI] or [LO] and press [Set] briefly�
[HI] = maximum value, [LO] = minimum value�
Delete memory:
►
Select [HI] or [LO]�
►
Press [Set] and keep it pressed until [----] is displayed�
►
Press [Mode/Enter] briefly�
It makes sense to delete the memories as soon as the unit works under
normal operating conditions for the first time�