9.4.2 Scaling of the analogue value for temperature
►
Select [SEL2] and set [TEMP]�
►
Select [OU2 ] and set the function:
[I] = current signal proportional to temperature (4…20 mA);
[U] = voltage signal proportional to temperature (0…10 V)�
►
Select [ASP] and set the value at which the minimum output value is
provided�
►
Select [AEP] and set the value at which the maximum output value is
provided�
9.5 User settings (optional)
9.5.1 Determine the standard unit of measurement for volumetric flow
►
Select [Uni] and set the unit of measurement: [GPm] or [GPh]�
The setting only has an effect on the volumetric flow value� The counter
values (consumed quantity) are automatically displayed in the unit of meas-
urement providing the highest accuracy�
9.5.2 Configuration of the standard display
►
Select [SELd] and determine the standard process category�
[FLOW] = display shows the current volumetric flow value in the stand-
ard unit of measurement�
-[TOTL] = display indicates the current meter count in gal or 1000 gal�
-
[TEMP] = display indicates the current medium temperature in °F.
►
Select [diS] and determine the update rate and orientation of the display:
[d1] = update of the measured values every 500 ms�
[d2] = update of the measured values every 1000 ms�
[d3] = update of the measured values every 2000 ms�
[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°.
[OFF] = the display is switched off in the operating mode�
9.5.3 Setting the output logic
►
Select [P-n] and set [PnP] or [nPn]�
9.5.4 Calibration of the curve of measured values
►
Select [CGA] and set the value between 60 % und 140 % einstellen
(100 % = factory preset)�