9.3.2 Settings for quantity monitoring using the preset meter
►
Select [OU1] and set [ImP]�
►
Select [ImPS] and set the volumetric flow quantity at which output 1
switches (→ 9.7).
►
Select [ImPR] and set [no]
> Pulse repetition is not active� The output switches ON if the value set in
[ImPS] is reached� It remains switched until the meter is reset�
9.3.3 Settings for meter reset controlled by the program
►
Select [rTo] and continue with a) or b)�
a) Reset the meter manually
►
Press [Set] until [rES�T] is displayed, then press [Mode/Enter] briefly�
b) Enter the value for time-controlled reset
►
Press [Set] until the requested value is displayed (intervals from 1 hour
to 8 weeks), then press [Mode/Enter] briefly�
9.3.4 Switch off the meter reset
►
Select [rTo] and set [OFF]� The meter is only reset after overflow
(= factory setting)�
9.3.5 Settings for meter reset by an external signal
►
Select [OU2] and then [InD]�
►
Select [Din2] and set the reset signal:
[HI] = reset for high signal,
[LOW] = reset for low signal,
[+EDG] = reset for rising edge,
[-EDG] = reset for falling edge�
9.4 Settings for temperature monitoring
9.4.1 Settings for limit value monitoring with OUT2
►
Select [SEL2] and set [TEMP]�
►
Select [OU2] and set the switching function:
[Hno] = hysteresis function/normally open,
[Hnc] = hysteresis function/normally closed,
[Fno] = window function/normally open,
[Fnc] = window function/normally closed�
►
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output switches back�