20
9.2 Settings for volumetric flow monitoring
9.2.1 Settings for limit value monitoring with OUT1
►
Select [OU1] and set the switching function:
[Hno] = hysteresis function/normally open,
[Hnc] = hysteresis function/normally closed,
[Fno] = window function/normally open,
[Fnc] = window function/normally closed�
►
Select [SP1] and set the value at which the output switches�
►
Select [rP1] and set the value at which the output switches back�
9.2.2 Settings for limit value monitoring with OUT2
►
Select [SEL2] and set [FLOW]�
►
Select [OU2] and set the switching function:
[Hno] = hysteresis function/normally open,
[Hnc] = hysteresis function/normally closed,
[Fno] = window function/normally open,
[Fnc] = window function/normally closed�
►
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output switches back�
9.2.3 Scaling of the analogue value for volumetric flow
►
Select [SEL2] and set [FLOW]�
►
Select [OU2] and set the function:
[I] = current signal proportional to volumetric flow (4…20 mA);
[U] = voltage signal proportional to volumetric flow (0…10 V)�
►
Select [ASP] and set the value at which the minimum output value is
provided�
►
Select [AEP] and set the value at which the maximum output value is
provided�
9.3 Settings for monitoring of consumed quantities
9.3.1 Settings for quantity monitoring by pulse output
►
[Select [OU1] and set [ImP]�
►
Select [ImPS] and set the volumetric flow quantity at which 1 pulse is
provided (→ 9.7).
►
Select [ImPR] and set [YES]
> Pulse repetition is active� Output 1 provides a counting pulse when the
value set in [ImPS] is reached�