31
UK
11.2 Reading the set parameters
► Press [Mode/Enter] briefly to scroll the parameters�
► Press [Set] briefly to indicate the corresponding parameter value for about 15 s�
After another 15 s the unit returns to the Run mode�
11.3 Changing the display unit in the Run mode
(= switching between length indication (cm / inch) and percentage)�
► Press [Set] briefly in the Run mode�
> The selected unit is displayed for 15 s, the corresponding LED is lit� With each
push of the button the display type is changed�
11.4 Error indications
Possible cause
Recommended measures
[E�000]
Fault in the electronics�
Replace the unit�
[E�031]
Probe detached from the unit;
possibly incorrect setting of the
probe length�
Check whether the probe is still at-
tached to the unit�
Check the parameter [LEnG]�
[E�033]
Measurement disturbed by
foam formation or strong
turbulence�
• Install the unit in a still pipe or bypass�
• Set or increment [dFo]
(→ 10.6.6).
Measurement disturbed by
separation layers (e�g� oil layer
on water)�
Remove the oil layer by suction, stir the
medium, verify the composition�
Rod or process connection
soiled�
Clean the rod and the process connec-
tion, carry out a reset�**
Installation conditions were not
adhered to�
Observe the notes in "Installation"
(→ 6).
Probe length set incorrectly�
Correct the settings (→ 10.2), then
carry out a reset�**
[E�034]
Atypical, abrupt level changes�*
Check the dynamics (if necessary, use
a still pipe or bypass), then carry out
a reset�**
[SCx]
Flashing: short circuit in switch-
ing output x�
Remove the short circuit�
[SC]
Flashing: short circuit in all
switching outputs�
Remove the short circuit�
[PArA]
Faulty data set
Reset to factory settings (→ 10.7).