Operating instructions 

Capacitive sensors

KG5070

704433 / 01  06 / 2009

UK

Содержание Efector 150 KG5070

Страница 1: ...Operating instructions Capacitive sensors KG5070 704433 01 06 2009 UK ...

Страница 2: ...4 4 1 Notes on flush and non flush installation 4 4 2 Notes on installation in tanks 5 4 3 Notes on laying of the connection cable 5 5 Electrical connection 6 4 1 Wiring 6 6 Operating and display elements 6 7 Operating modes 7 7 1 Settings 7 8 Operation 9 9 Maintenance repair and disposal 9 10 Approvals 10 11 Terms 10 ...

Страница 3: ...sure that the product is suitable for your application without any restrictions The unit conforms to the relevant regulations and EU directives Improper use or non intended use may lead to malfunctions of the unit or to unwanted effects in your application That is why installation electrical connection set up operation and mainte nance of the unit must only be carried out by qualified personnel au...

Страница 4: ... to be detected by means of programming buttons 4 Installation 4 1 Notes on flush and non flush installation For flush installation of non flush units the sensor properties change and the sensor can remain permanently switched loss of function Respect the open space around the sensing face flush 1 non flush 2 Adhere to the minimum distances when mounting several sensors of the same type ...

Страница 5: ...with the medium only for non metallic tanks In contact with the medium In case of liquids use a mounting adapter e g E43900 4 3 Notes on laying of the connection cable Lay the cable as straight as possible and do not coil it If necessary cut the cable to the required length 3x Sn ...

Страница 6: ...n of electrical equipment must be adhered to Disconnect power Connect the unit 4 1 Wiring p switching type FPKG BN brown BK black BU blue 6 Operating and display elements LED ring green yellow green operation indication yellow output status indication 1 sensing face 2 threaded sleeve 3 programming button OUT ON 4 programming button OUT OFF 5 ...

Страница 7: ...s yes 7 Operating modes 7 1 Settings Basic teach empty state Using the basic teach empty state the unit suppresses the wall of the tank The basic teach empty state resets the unit an adjustment teach already carried out is deleted Normally open unit output closes when the tank is full Press OUT OFF for min 2 s max 6 s While pressing the pushbutton the LED flashes slowly After releasing the pushbut...

Страница 8: ...O the LED lights for NC it goes out Normally open unit Press OUT ON for min 6 s While pressing the pushbutton the LED first flashes slowly after 6 s more quickly After releasing the pushbutton the LED lights continuously Normally closed unit Press OUT OFF for min 6 s While pressing the pushbutton the LED first flashes slowly after 6 s more quickly After releasing the pushbutton the LED goes out Ad...

Страница 9: ...cknowledgement LED state yellow changes for a short time the lit LED goes out briefly or the LED which is not lit lights briefly To unlock repeat this step If the unit does not react it may be locked 8 Operation Check whether the unit operates correctly Bring about a sensor response by taking suitable measures Display by LED LED yellow OFF switching output disabled LED yellow ON switching output e...

Страница 10: ...ne output blocked Programmable Choice between normally closed or normally open Positive switching Positive output signal to L Negative switching Negative output signal to L Power on delay time The time the sensor needs to be ready for operation after application of the opera ting voltage in the millisecond range Hysteresis The difference between the switch on and the switch off point Leakage curre...

Страница 11: ...ent lamps electronic relays and low resistance loads may cause this protection to cut in and turn the sensor off Operating voltage The voltage range in which the sensor functions safely A stabilised and smoothed direct voltage should be used Take into account residual ripple Technical data and further information at www ifm com Select your country Data sheet direct ...