PWM in the ecomatmobile controller
Current control with PWM
177
9.2.4
Function OUTPUT_CURRENT
Contained in the library:
ifm_CRnnnn_Vxxyyzz.LIB
Available for the following devices:
•
ClassicController: CR0020, CR0032, CR0505
•
ExtendedController: CR0200, CR0232
•
SafetyController: CR7020, CR7021, CR7032, CR7200, CR7201, CR7232, CR7505, CR7506
•
SmartController: CR2500, CR2501, CR2502
Function symbol:
OUTPUT_CURRENT
ENABLE
ACTUAL_CURRENT
OUTPUT_CHANNEL
DITHER_RELATED
Description
OUTPUT_CURRENT handles the current measurement in conjunction with an active PWM channel.
The function provides the current output current if the outputs are used as PWM outputs. The current
measurement is carried out in the device, i.e. no external measuring resistors are required.
Parameters of the function inputs
Name
Data type Description
ENABLE
BOOL
TRUE: function is executed.
FALSE: function is not executed
OUTPUT_CHANNEL BYTE PWM
output
channel
(0...x: values depend on the device)
Parameters of the function outputs
Name
Data type Description
ACTUAL_CURRENT WORD Output current in [mA].