
18
ifm
Operating Instructions IO-Link Master with PROFINET interface DataLine 4 Ports IP 65 / IP 66 / IP 67 (AL1300)
05 / 2018
Electrical connection
Connect the device
>
6.5
Connect the device
2580
► Disconnect power.
► Connect the unit via M12 socket X31 to 24 V DC
(20...30 V SELV/PELV; according to EN61010-1, secondary circuit
with maximum 30 V DC derived from applied voltage up to 300 V
of overvoltage category II).
Tightening torque: 0.6...0.8 Nm
Maximum cable length: 25 m
► To connect the device , use M12 connectors with protection rating
IP 65 / IP 66 / IP 67 or higher (
→
Accessories
(
)).
If the port X01...X04 will be used as IO-Link ports Class B:
► Connect adapter for Port Class B operation to 24 V DC
(20...30 V SELV/PELV; according to EN61010-1, secondary circuit
with maximum 30 V DC derived from applied voltage up to 300 V
of overvoltage category II) (
→
IO-Link ports
(
Tightening torque: 0.6...0.8 Nm
When using connectors longer than 25 m keep in mind the voltage drop as well as the
required minimum voltage supply of the AL1300.