Configuration
>
8.2.3
Configure the interface to the SmartObserver
12743
In order to set the parameters of the interface to the SmartObserver:
►
Select the [LineRecorder] menu.
>
The page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[IP address SmartObserver]
IP address of the laptop/PC where the
SmartObserver is installed
e.g. 192.168.0.100
[Port SmartObserver]
Port address that is used to send
process data to the SmartObserver
1
...
65535
Default value: 35100
[Source ID SmartObserver]
Source identifier with which the process
data of the device is indicated in the
SmartObserver (String32)
[Port x. LR events]
Operating mode of the IO-Link port
(x = 1...8)
Disabled
Cyclic transfer of the process data
Enabled
Event-based transfer of the process
data
[Port x. LR cycle time (ms)]*
Cycle time of the IO-Link interface for
cyclic transmission of the process data
between the IO-Link master and the
SmartObserver
(x = 1...8)
Disabled
no data transmission
1000
...
60000
1000 ms
...
60000 ms
* ... parameter only valid if parameter [PortX. LR events] = Disabled
After changing the parameter [Port SmartObserver] or [Source ID SmartObserver], it can take
120 seconds before the device establishes a new TCP connection.
To prevent the delay:
► Reboot the device after the parameter change.
►
Store changed values on the device.