Operating Instructions 

Compact Overfill Sensor, Float Type 

MAXIMAT VK C... 

with integrated mesuring Transducer, DIBT Approval Z-65.11-355 

 

Safety Precautions 

• 

Installation, initial start-up and maintenance may only be 
performed by trained personnel! All applicable European and 
national regulations regarding installation of electrical 
equipment must be adhered to. 

• 

The device may only be connected to supply power which 
complies with the specifications included in the technical data 
and on the serial plate! 

• 

The device must be disconnected from all sources of power 
during installation and maintenance work! 

• 

The device may only be operated under the conditions 
specified in the operating instructions! 

 

Functions Description 

The MAXIMAT VK C... compact overfill sensor is used as a fill-
level limit switch for permanently installed containers used for the 
storage of non-flammable, water endangering liquids. 
It is equipped with three different output circuits: 

• 

A binary output for controlling a coupling relay, or the digital 
input of a PLC 

• 

A 0 to 20 mA current output for controlling an analogue input 
channel, e.g. a programmed logic controller (PLC) 

• 

Self-monitoring measuring circuit in combination with the 
MAXIMAT SHR C... measuring transducer with 2-wire 
connection 

Note: 

Only for liquids with density greater than 

0.7g/cm³

 

The MAXIMAT VK C... compact overfill sensor is used also for oil, 
emulsion and other non-conductive liquids. 

 

Technical Data 

Supply power 

24 V DC ± 10% 
With current limiting or 250 mA fuse recommended 

Connected load 

Approx. 3 W 

Ambient temperature 

-20 to +60

° 

Container pressure 

Atmospheric (0.8 to 1.1 bar)

 

Terminal housing 

IP 65 

Terminals 

Screw terminals: IP 20 
Max. wire cross-section: 2.5 mm² 

Outputs 

Binary output: +DO/-DO max. 20 mA / 24 V +AO / -AO  
0 to 20 mA 
Output for MAXIMAT SHR C... measuring transducer 

DIP Switch 
Operating Mode 

DIP1 

DIP2 

DIP3 

DIP4 

Binary output 

ON 

ON 

ON 

OFF 

Current output/PLC  OFF 

OFF 

OFF 

OFF 

MAXIMAT SHR C 

OFF *  OFF *  OFF *  OFF * 

* Default setting

 

Note: 

 

Be sure to examine the DIP switch settings before 
switching supply power on! 

Indicators 

Green LED on the connector PCB:

 

• 

Run = LED illuminated 

• 

Alarm / error = LED off 

 
Measuring circuit for use with SHR C... transducer 

Max. cable inductance: 

approx. 5 mH

 

Max. cable capacitance: 

approx. 0.5 

µ

F

 

Measuring circuit cable length 

Max. 300 m 
Min. wire cross-section: 0.5 mm² 
 

CE mark

 

In accordance with low-voltage directive (73/23/EWG), 
EMC directive (89/336/EWG) and 

• 

EN 50 082-2:1995 

• 

EN 55 011 (class A):1998 

 

DIBT Approval 

Approval no. 

Z-65.11-355

 for overfill sensors and leakage 

sensors in accordance with WHG §19

 

Note: 

The accompanying “General Building Supervisory Approval 
no. Z-65.11-355” is an integral part of the operating 
instructions and all stipulations contained therein must be 
adhered to! 
 
 
 
 
 