Operating Instructions

 

ES1S

 Electrode Controls

 

 

Safety Precautions 

• 

The device may only be connected to supply voltage which is in 
compliance with the technical data shown on the serial plate! 

• 

Installation, initial start-up and maintenance may only be 
performed by trained personnel! 

Technical Data

 

Power Supply 

230 V AC, +/-10%, 50-60 Hz 
Optional: 24, 115 V AC or 24 V DC +/-10% 
See serial plate on device. 

Power Consumption 

approx. 2 VA 

Ambient Temperature 

-15 to +45°C 

Housing 

22.5 x 75 x 100 mm, IP40 
Quick mount to standard rail 
DIN EN 50 022 (35 x 7.5 mm top-hat rail) 
or 88 x 150 x 130 mm, IP55 for surface mounting 

Terminals 

IP20, screw terminals 
Conductor cross-section: max. 2.5 square mm 

Measuring Circuit 

Electrically isolated 
Alternating voltage < 6V / < 2 mA 

Cable Length 

max. 300 m (for highly conductive liquids) 
See figure 1. 
min. conductor cross-section: 0.5 square mm, shielded 

Measuring Functions 

MIN-MAX control, 
MIN control or MAX control 

Sensitivity 

Two adjustable ranges 
1 to 70 k

  /  5 to 150 k

 

Can be selected / adjusted with DIP switch / potentiometer 
(full left turn / anti clockwise  = min. sensitivity) 

Reset Hysteresis 

approx. 20% of the selected sensitivity value 

Relay Outputs 

2 ea. floating changeover contacts 
AC: max. 250 V, 5 A, 500 VA 
DC: max. 125 V, 1 A, 40 W

Operating Principle 

Working current / closed-circuit current 
selectable with DIP switch 

Delay 

ON delay / OFF delay: 0.5 to 3 sec. 
adjustable with potentiometer (full left = approx. 0,5 sec.) 

Status Indication 

1 ea. "on" LED, 1 ea. switching status LED 

CE Mark of Approval 

In accordance with low-voltage directive (73/23/EWG), 
EMC directive (89/336/EWG) and 

• 

EN 50 082-2:1995 

• 

EN 55 011 (Class A): 1991 

• 

EN 61010-1: 1993 

Applications Limits 

Conductive liquid-level controls are 

not

 suited for liquids which 

contain oil or grease, or which may cause electrically insulating 
deposits at the electrodes. 

Functional Description 

ES1S electrode controls function in accordance with the 
conductive principle, i.e. the electrical conductivity of the liquid to 
be monitored is used to establish an electrical connection between 
the immersed electrodes. 

Measuring Ranges 

ES1S electrode controls can be used for liquids with a resistance 
between the electrodes of less than 150 k

 (observe maximum 

cable length!). 

Controls 

Intermittent switching (minimum / maximum liquid level) with three 
electrodes 
Monitoring of a specific fill level (overflow / empty alarm) with two 
electrodes. A metal container can be used as the reference 
electrode. 
 

Electrical Connections 

 

MAX Electrode 

MIN Electrode 

Ref. Electrode 

12 

11 

14 

24 

21 

22 

E0 E1 E2

L+ N-

Control Voltage 

Filling Pump 
Relay / Contactor 

Filling pump relay/contactor pulls 
in when MIN electrode is exposed, 
... and is released when  
MAX electrode is immersed. 

ON
OFF

1

K

Power Supply

   L1  N   
   +    -    

 

Wiring Diagram 1: Filling the Container 

 

MAX Electrode 

MIN Electrode 

Ref. Electrode 

Power Supply 

   L1  N   
   +    -    

12

11

14

24

21

22

E0 E1 E2

L+ N-

Control Voltage 

Discharge Pump
Relay / Contactor 

Discharge pump relay/contactor pulls  
in when MAX electrode is immersed, 
... and is released when  
MIN electrode is exposed. 

OFF

ON

1

K

 

Wiring Diagram 2: Draining the Container