SINGLE SETPOINT BEHAVIOR - When configured
for
Single Setpoint
operation
(step #4, page 19)
,
the
degree icon will blink when the large number is display-
ing room temperature and will remain solid when dis-
playing the heating or cooling setpoint. In the Auto and
Program On modes the deadband is enforced both
above and below the setpoint. To avoid short cycling,
a deadband of at least two degrees is recommended
(step #8, page 20)
. To display the room temperature
press and hold the MODE button for two seconds.
Release the MODE button to return to the normal
display.