About Advanced Features & Operation
OUTSIDE SENSOR - To view an Outside Sensor
(step #12, page 21)
, enter the Advanced Setup by
pressing and holding the MODE button. While
holding MODE, press the FAN button for 5 seconds
to enter Setup screens. Advance to setup step #12
by repeatedly pressing the MODE button. If an
optional outside sensor is connected, the outside
temperature will appear in the clock display.
DUCT SENSOR
(P/N G100-71520307)
- The
thermostat is programmed from the factory to auto-
Page 31
matically recognize when a Duct
Sensor is connected (
step #12, page
21).
The Duct Sensor measures indoor
air temperature and sends this infor-
mation to the thermostat; it measures
temperature with a range of 32 to
99 F.
The Duct Sensor should be con-
nected to the thermostat using solid
conductor CAT 5, CAT 5e, or CAT 6 type network
communication cable. This is an unshielded cable with
four twisted pairs of 24 gauge solid wire;
DO NOT use
stranded cable
. The cable length should not exceed
250 feet. If less than 75 feet of cable is required to
connect the thermostat to the Duct Sensor, a three
conductor thermostat cable (18-24 gauge) may be
used; this cable is NOT suitable for any length greater
than 75 feet.
IMPORTANT: Do no use shielded wire. Do not run
sensor wiring in the same conduit as the 24VAC therm-
ostat wiring. Electrical interference may cause the
sensor to give incorrect temperature readings.
See the Duct Sensor instructions for further details.
Digital Sensor
High Temp. Heat
Shrink Tubing
Plenum Rated
Cable
Red
White
Black