PROGRAMMING NOTES
You will be prompted to enter both heat and cool
setpoints even if the thermostat is configured for
heat only, or cool only.
Heat & Cool setpoints for Occupied 1 are the same for
each day. Heat & Cool setpoints for Occupied 2 & 3 can
be adjusted differently for each day, if desired.
If the start time is set for later than the stop time,
the
program will run from the start time to midnight and from
midnight to the stop time on the same day.
For example:
9:00pm start, 8:00am stop, on MTWTF. This program
will run from 12:00am MTWTF to 8:00am MTWTF and
again from 9:00pm MTWTF to 12:00pm MTWTF.
The Unoccupied settings take effect at all times when:
(
1
) the program is on
and
(
2
) the current time is outside
a preset occupied period. For this reason start and stop
times aren’t necessary for unoccupied.
If the
same
start and stop times are programmed in for
an occupied period, then it will run 24 hours.
If one occupied period starts and stops within another
occupied period, the lower occupied # has priority.
example: If Occupied 3 is programmed to be “on” 24
hours, and Occupied 2 is programmed to run that day,
then Occupied 2 settings will take over from Occupied 3
between Occupied 2 start and stop times.
For
If only 1 Occupied period is selected, the Occupied 2 & 3
steps will be skipped. Further, if only 2 occupieds are
selected, the Occupied 3 steps will be skipped.
Programming
Occupied & Unoccupied Periods
When the time period programming for Unoccupied is in
the Override mode (
see page 12
), the Heat & Cool
setpoints for Occupied 1 are used.
Page 17