p.81
A registered card is not authenticated.
6.2
Please check if wiring between a reader and the system.
See
[Installation of the Product ] > [Wiring] > [Reader Wiring]
of the manual and check wirin
g between the reader and the device.
If you use a separate power for a reader not connecting to the device, GND of the
reader must be connected to GND of the device.
6.3
Please check if software settings are good.
1.
In the case of using iTDC, check if controller definition of a software is set to iTDC-SR. If
it is iTDC-SR, change it to iTDC.
2.
In the case of using iTDC-SR, check if controller definition of a software is set to iTDC. If
it is iTDC, change it to iTDC-SR.
6.4
Remove noise.
1.
Shield wire and extra wire of cable to GND.
2.
Use repeater.
3.
See
[INSTALLATION TIPS & CHECK POINT] > [Check Points before Installation] > [Recom
mended Cable Type and Permissible Length of Cable]
and check distance between a re
ader and the device.
If the problem persists, please contact service center
7
A registered card is not authenticated.
7.1
Check data format setting of the device.
1.
See
[INSTALLATION OF THE PRODUCT] > [Device Setting] >[26Bit / 34Bit Wiegand Setti
ng]
and check input data format of reader port of the device.
I.
In the case of 26 bit
Cards are not authenticated if you use 34bit Wiegand format reader such as SR10/
20/30 and SRK101.
Содержание Star iCON100SR
Страница 1: ......
Страница 26: ...INSTALLATION OF THE PRODUCT 8 p 20 1 Dimension Unit inch mm...
Страница 45: ...SETTING CHANGES 12 p 39...
Страница 47: ...p 41 Setup Menu F1 1 Setup Menu F1...
Страница 54: ...SETTING CHANGES p 48 2 1 Time Schedule...
Страница 71: ...p 65 Setup Menu F4 4 Setup Menu F4...