56
IDS X-Series Training v2.7
Sub-location 3: Signal Power of Receiver
NOTE: This menu is only available with the LCD keypad. The user will need to trigger the zone to
get a signal power update.
Go to sub-location 3.
1.
Enter [*] to enter signal strength testing.
2.
Enter or scroll to the zone to be deleted.
3.
Press the [*] key to select the zone.
4.
Trigger the device and the display will show the signal strength on the first row.
Sub-location 4: Supervision Monitoring
Supervision is the monitoring of wireless devices to make sure that they remain in communication with the
system. In this sub-location you can choose the time that the alarm waits before raising a trouble condition
if it has not received a signal from a device.
Your options are:
Default: 2 (24 hour)
Valid range: 1 – 2
Note: When entering this sub-location the first supervision time displayed is the entered time.
Note: This is note used with Xwave
2
devices.
Sub-location 5: Xwave
2
Zone Properties
Certain compatible Xwave
2
devices allow you to change detector properties from the panel. The following
options can be set:
Option Default
Description
1
N
Device LED can be enabled = Y or disabled = N
2
N
Set sensitivity pulse count. See the detector manual that is allocated to the zone for options N
= Default option Y =second option
Reporting Codes
In the following locations, 261 to 335, the value of the reporting codes are entered for reporting formats
other than SIA and Contact ID. For example formats like, FBI 4x2.
[INSTALLER CODE] [*] [LOCATION] [*] [SUB-LOCATION] [*] [REPORTING CODE] [*]
Location 261 to 264 Stay Zone Reporting Codes
Location Type: Extended
Each location represents a set of 16 zones.
Locations to enter reporting codes if you want to report stay zones to the control room.
Location
Profile
Zones
Location
Profile
Zones
261
1
1 to 16
263
3
33 to 48
262
2
17 to 32
264
4
49 to 64
Default is 00
Valid Range: 00 - FF
Option
Description
1
3 Hours
2
24 Hours