Operating Instructions

 

IDEM Safety Switches

 

 NET-BOX-CS

 

 

102638 2305 NET-BOX-CS Operating Instructions 

 

10

 

7

 

Diagnostic Indication 

 

LED 

Function 

Colour 

DS 

Device Status 

Red/Green 

PS 

Module Status 

Red/Green 

PN 

Network Status 

Red/Green 

L1 

Link 1 

Amber/Green 

L2 

Link 2 

Amber/Green 

 

LED 

LED State 

Comment 

DS 

Green 

Device running 

Red 

Internal fault detected 

MS 

Green 

Connection to PLC, Run state 

Green Flash 

Connection to PLC, Idle state 

Red 

Major Fault 

Red Flashing 

Recoverable fault, check PLC/NET-BOX configuration 

NS 

Off 

No IP address set 

Green 

Online, connection(s) established 

Green flash 1Hz 

Online, no connections established 

Red 

Network fault 

Red flash 

Connection timed out. 

L1/L2 

Off 

No Ethernet link detected 

Amber 

Ethernet link detected 

Amber flash 

Ethernet data transfer 

 

 

 

Diagnostic LED’s are not reliable indicators and cannot be guaranteed to provide accurate 

information. They should only be used for general diagnostics during commissioning or 
troubleshooting. Do not attempt to use LEDs as operational indicators. 

 

 

Содержание NET-BOX-CS

Страница 1: ...nstructions To request this document in other languages please contact info idemsafety com IDEM Safety Switches NET BOX CS Safety IO Standard IO and Integrated EtherNet IP with CIP Safety Operating In...

Страница 2: ...col Setup 4 Network Address Setup Initial Setting 5 Setting via DIP Switch 5 Setting via DHCP 6 Studio 5000 Ethernet IP Configuration 7 Factory reset 9 Functional Tests 9 6 Data Map 9 7 Diagnostic Ind...

Страница 3: ...idiaries and affiliates are not in a position to guarantee all of the characteristics of a given system or product not design by IDEM All relevant safety regulations and standards are to be observed T...

Страница 4: ...ISATEUR Observe the county specific regulations when installing the device Repair or modification of the NET BOX is not allowed unless authorised by IDEM and carried out according to operating guideli...

Страница 5: ...irements for UL a class 2 power supply must be used INFORMATION When multiple devices are used in a daisy chain arrangement the power bus may be forwarded via the NET BOX device See technical specific...

Страница 6: ...ASYNC parameter value of 1 Configuring an originator with connection data and or target configuration data must be downloaded to the target so it can be tested and verified Only then can SCIDs from t...

Страница 7: ...the final step if the device is powered Remove the lid screws and turn over the NET BOX Lid to locate the DIP switches see below Using a small tool push the required switches to the ON position to set...

Страница 8: ...entify the NET BOX select the NET BOX in the Discovery History window and click Add Relation 4 Configure the required IP address setting in the pop up window and click OK 5 Open an internet browser an...

Страница 9: ...Configuration 1 Download the EDS file for the NET BOX and import to application control software 2 Open or create a project with the PLC CPU Partner and Ethernet IP modules added 3 Right click the Et...

Страница 10: ...customisable NET BOX CS used as example only and set the previously configured IP address 6 Change the Safety Network Number SNN to match that of the controller PLC 7 On the Safety tab uncheck the Con...

Страница 11: ...ce has been installed and setup within the EtherNet IP CIP Safety application control software the following checks are necessary to ensure correct operation of the system Secure mounting of NET BOX w...

Страница 12: ...on to PLC Idle state Red Major Fault Red Flashing Recoverable fault check PLC NET BOX configuration NS Off No IP address set Green Online connection s established Green flash 1Hz Online no connections...

Страница 13: ...ge 24V DC Input Rated Current 2 mA Standard Outputs Output Rated Voltage 24V DC sourced from power connectors Output Maximum Current 500 mA single 1 5 A group OUT1 4 OUT5 8 Test Outputs Parameter Unit...

Страница 14: ...altitude 2000 m Shock and Vibration Tested in accordance with IEC 60068 2 6 and IEC 60068 2 27 Pollution Degree Degree 2 EN 60664 Storage and Operation Reliability Safety Data EN ISO 13849 1 Category...

Страница 15: ...Operating Instructions IDEM Safety Switches NET BOX CS 102638 2305 NET BOX CS Operating Instructions 13 NOTES...

Страница 16: ...BOX THE LISTED DEVICES CONFORM TO THE ESSENTIAL HEALTH AND SAFETY REQUIREMENTS OF THE FOLLOWING EUROPEAN DIRECTIVES AND STANDARDS DIRECTIVES Machinery Directive 2006 42 EC EMC Directive 2014 30 EU ST...

Отзывы: