5 HG1P
35-84
WindO/I-NV4 User’s Manual
5.8 Wiring
●
HG1P Optional Cable (HG9Z-XCP13/-XCP15/-XCP17)
This cable connects the HG1P and external devices.
■
Specifications
■
Outline Drawing
■
Connector Wiring Table
CAUTION
• Turn off the power supply before wiring.
• Make the wiring as short as possible and run all wires as far away as possible from high-voltage
and large-current cables. Follow all the procedures and precautions when wiring the HG1P.
• Separate the HG1P power supply wiring from the power lines of I/O devices and motor
equipment.
• Connect the functional ground terminal to make sure of correct operation.
Communication Interface
Serial Interface (RS422/485) or Ethernet Interface
Connector for the External Devices
D-sub 25-pin Male Connector (Jackscrew M2.6)
Length
3m, 5m, 7m
Cable Length 3m, 5m, 7m
1
13
25
14
Connector for the External Devices
(View of mating surface of the removable connector)
No.
Name
Function
No. Name
Function
1
FG
Frame Ground
14 NC
-
2
RDB-/TP1-
Receive Data (-)
15 NC
-
3
RDA+/TP1+ Receive Data (+)
16 NC
-
4
SDB-/TP0-
Send Data (-)
17 NC
-
5
SDA+/TP0+ Send Data (+)
18 C_NC1
Selector Switch Contact 1 (NC)
6
SG
Communication Signal Ground
19 C_NO1
Selector Switch Contact 1 (NO)
7
NC
-
20 C_C1
Selector Switch Contact 1 (COM)
8
NC
-
21 B_NO2
Enabling Switch Contact 2 (NO)
9
B_NO1
Enabling Switch Contact 1 (NO)
22 B_C2
Enabling Switch Contact 2 (COM)
10 B_C1
Enabling Switch Contact 1 (COM)
23 A_NC21 Emergency Stop Switch Contact 2 (NC)
11 A_NC11
Emergency Stop Switch Contact 1 (NC)
24 A_NC22 Emergency Stop Switch Contact 2 (NC)
12 A_NC12
Emergency Stop Switch Contact 1 (NC)
25 DC24V+ HG1P 24V DC Power Supply (+)
13 DC24V-
HG1P 24V DC Power Supply (-)
Содержание WindO/I-NV4
Страница 1: ...B 1701 16 User s Manual...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic ANSI 1257 Cyrillic ANSI 1251...
Страница 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Страница 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Страница 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Страница 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Страница 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Страница 522: ...5 Key Button 8 102 WindO I NV4 User s Manual Password Input These keys switch the user on the Password Input Screen...
Страница 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Страница 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Страница 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Страница 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Страница 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Страница 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Страница 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Страница 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...