S
MART
AXIS P
RO
/ L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
4-19
4: O
PERATION
B
ASICS
Start/Stop Operation
This section describes operations to start and stop the SmartAXIS and to use the stop and reset inputs.
Start/Stop Schematic
Start/Stop Operation Using WindLDR
The SmartAXIS can be started and stopped using WindLDR run on a Windows computer connected to the SmartAXIS. When the
Start
button is pressed in the menu bar shown below, start control special internal relay M8000 is turned on to start the
SmartAXIS. When the
Stop
button is pressed, M8000 is turned off to stop the SmartAXIS.
1.
Connect the computer to the SmartAXIS, start WindLDR, and power up the SmartAXIS.
2.
Check that a stop input is not designated using
Configuration
>
Run/Stop Control
>
Stop and Reset Inputs
. See "Stop
Input and Reset Input" on page 5-4.
Note:
When a stop input is designated, the SmartAXIS cannot be started or stopped by turning start control special internal relay M8000 on or off.
3.
Select
Online
from the WindLDR menu bar.
The Online tab appears.
4.
Click the
Start
button to start operation, then the start control special internal relay M8000 is turned on.
5.
Click the
Stop
button to stop operation, then the start control special internal relay M8000 is turned off.
The PLC operation can also be started and stopped while WindLDR is in the monitor mode. Select
Online
>
Monitor
>
Monitor
and click the
Start
or
Stop
button.
Note:
Special internal relay M8000 is a keep type internal relay and stores the status when power is turned off. M8000 retains its previous status
when power is turned on again. However, when the backup battery is dead, M8000 loses the stored status, and can be turned on or off as
programmed when the SmartAXIS is powered up. The selection is made in
Configuration
>
Run/Stop Control
>
Run/Stop Selection at
Memory Backup Error
. See "Run/Stop Selection at Memory Backup Error" on page 5-5.
The backup duration is approximately 30 days (typical) at 25°C after the backup battery is fully charged.
Make sure of safety before starting and stopping the SmartAXIS. Incorrect operation of the SmartAXIS may cause
machine damage or accidents.
Caution
The start/stop circuit of the SmartAXIS consists of three
blocks; power supply, M8000 (start control special
internal relay), and stop/reset inputs. Each block can be
used to start and stop the SmartAXIS while the other
two blocks are set to run the SmartAXIS.
Power
Supply
M8000
Stop
Input
Reset
Input
Start
Start Control
PLC
WindLDR
Содержание SmartAXIS FT9Z-1A01
Страница 1: ...FT9Y B1378 7...
Страница 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Страница 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Страница 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Страница 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Страница 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Appendix 15 APPENDIX European Font ISO 8859 1 Cyrillic Font ANSI 1251...
Страница 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Страница 393: ......