13: T
ROUBLESHOOTING
13-10
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
Troubleshooting Diagram 2
The Run LED [RUN] is not On
The run LED [RUN] turns on when the PLC is running.
Is the stop/reset input
switch or the function switch
used to run/stop the PLC?
The run LED [RUN] is not on.
Click the Start button in WindLDR on a
computer connected to the FC6A Series
MICROSmart.
END
Call IDEC for assistance.
Is the error LED [ERR] on?
NO
See Troubleshooting Diagram 3,
"The Error LED [ERR] is On"
YES
Is the run LED [RUN] on?
Monitor M8000 (start control special
internal relay) using WindLDR.
Is M8000 on?
Turn on M8000 using WindLDR.
Is the run LED [RUN] on?
Turn off the stop/reset input and set the
function switch to "1."
Is the run LED [RUN] on?
YES
NO
YES
YES
NO
NO
YES
Note:
The Start button is found in the WindLDR menu bar.
NO
YES
Note:
To monitor M8000, from the WindLDR menu bar, select Online >
Monitor > Monitor, then Online > Custom > New Custom Monitor. Enter
M8000 in the Device box in the Custom Monitor dialog box.
Note:
To turn on M8000, enter 1 in the Current Value box in the
Custom Monitor dialog box.
NO
Содержание MICROSmart FC6A Series
Страница 1: ...B 1722 8 FC6A SERIES User s Manual...
Страница 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Страница 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...