Settings tab
6. Output pulse frequency
Specifies the frequency of the pulses to output.
The frequency is specified between 15 Hz and 5 kHz in 1 Hz increments.
The pulse frequency error is within ±5%.
7. Pulse width ratio
This setting specifies the ON ratio (duty cycle) for the pulse frequency to output.
If the configuration mode is
FC6A Standard Mode
, the pulse width ratio is specified between 0.1% and 100.0% in 0.1%
increments. If the configuration mode is
FC4A Compatible Mode, FC5A (except FC5A-D12X1E) Compatible Mode
, or
FC5A-D12X1E Compatible Mode
, the pulse width ratio is specified between 1% and 100% in 1% increments.
8. Pulse counting
Enables or disables pulse counting.
If
Enable pulse counting
is specified, the number of pulses specified by the preset value (9) is output.
If
Disable pulse counting
is specified, pulses are continuously output while the PULS instruction input is on.
9. Preset value
When the setting for 8. Pulse counting is
Enable pulse counting
, this setting specifies the number of pulses to output.
10. Current value
Specifies the device (data register) that will store the number of pulses that were output.
The current value is updated when the PWM instruction is executed at each scan.
11. Error status
Outputs the error code that corresponds to the content of an error when there is an error in the settings. If a configuration error
occurs when the PWM instruction input changes from off to on, a user program execution error will occur and error code 20 will
be stored in D8006.
Error Code
Status
Description
0
Normal
—
1
Output frequency designation error
The pulse frequency was not set between 15 and 5,000.
2
Pulse width ratio designation error
The pulse width ratio was not set between 1 and 1,000.
4
Preset value designation error
If
Enable pulse counting
is specified, the preset value was not set between
1 and 100,000,000.
6.
7.
8.
9.
10.
11.
Содержание MICROSmart FC6A Series
Страница 1: ...B 1726 7 FC6A SERIES Ladder Programming Manual ...
Страница 8: ...Preface 7 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 32: ...1 OPERATION BASICS 1 20 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 96: ...3 INSTRUCTIONS REFERENCE 3 18 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 130: ...4 BASIC INSTRUCTIONS 4 34 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 158: ...6 DATA COMPARISON INSTRUCTIONS 6 10 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 192: ...9 SHIFT ROTATE INSTRUCTIONS 9 12 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 216: ...10 DATA CONVERSION INSTRUCTIONS 10 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 248: ...11 WEEK PROGRAMMER INSTRUCTIONS 11 32 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 272: ...12 DISPLAY INSTRUCTIONS 12 24 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 284: ...14 REFRESH INSTRUCTIONS 14 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 288: ...15 INTERRUPT CONTROL INSTRUCTIONS 15 4 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 294: ...16 COORDINATE CONVERSION INSTRUCTIONS 16 6 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 374: ...18 PULSE OUTPUT INSTRUCTIONS 18 78 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 Setting ...
Страница 450: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 502: ...25 DATA LOG INSTRUCTIONS 25 22 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 546: ...26 SCRIPT 26 44 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 574: ...27 FLOW CALCULATION INSTRUCTIONS 27 28 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 583: ...FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 28 9 28 USER DEFINED MACRO INSTRUCTION ...
Страница 584: ...28 USER DEFINED MACRO INSTRUCTION 28 10 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...
Страница 598: ...APPENDIX A 14 FC6A SERIES MICROSMART LADDER PROGRAMMING MANUAL FC9Y B1726 ...