5: U
SER
C
OMMUNICATION
I
NSTRUCTIONS
5-40
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
C
OMMUNICATION
M
ANUAL
FC9Y-B1730
User Communication Server
When a server connection is configured as the user communication server, a client device can access and communicate with the
FC6A Series MicroSmart. The FC6A Series MicroSmart communicates with the client device according to the settings configured in
the ETXD and ERXD instructions that are programmed for the server connection. The local host number and other communication
settings can be configured in the
Connection Settings
tab in the
Function Area Settings
dialog box.
Specifications (User Communication Server)
Note 1:
A maximum of eight connections can be allocated to user communication servers, and a maximum of eight client devices can
simultaneously connect to and communicate with the FC6A Series MicroSmart.
User Communication Server Receive Instruction (ERXD) Cancel Flag
The allocation of the user communication receive instruction cancel flags for each server connection is shown in the table below.
For details about the user communication receive instruction cancel flag, see "User Communication Receive Instruction Cancel
Flag" on page 5-22.
Item
User Communication Server
Local Host Port Number
2102 to 2109 (Can be changed between 0 and 65535)
Number of Clients That Can Simultaneously
Communicate with the FC6A Series
MicroSmart
One client per a user communication server (Note 1)
Receive Timeout Time
100 to 25,500 ms (100 ms increments)
Device Address
Description
M8200
User Communication Receive Instruction Cancel Flag (Connection 1)
M8201
User Communication Receive Instruction Cancel Flag (Connection 2)
M8202
User Communication Receive Instruction Cancel Flag (Connection 3)
M8203
User Communication Receive Instruction Cancel Flag (Connection 4)
M8204
User Communication Receive Instruction Cancel Flag (Connection 5)
M8205
User Communication Receive Instruction Cancel Flag (Connection 6)
M8206
User Communication Receive Instruction Cancel Flag (Connection 7)
M8207
User Communication Receive Instruction Cancel Flag (Connection 8)
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...