RS232C Line Control Signals
While the FC6A Series MicroSmart is in user communication mode, special data registers can be used to enable or disable DSR and
DTR control signal options for port 1 through port 3.
Line control signals cannot be used with RS485 communication.
The RS-232C communication cartridge (FC6A-PC1) RS signal is an always on output signal.
In the maintenance communication mode, DSR has no effect and DTR remains on.
Special Data Registers for Port 1 to Port 3 RS232C Line Control Signals
Special data registers D8104 through D8106 are allocated for RS232C line control signals.
Control Signal Status D8104
Special data register D8104 stores a value to show that DSR and DTR are on or off at port 1 through port 3.
The data of D8104 is updated at every END processing.
DSR Control Signal Status in RUN and STOP Modes
DTR Control Signal Status in RUN and STOP Modes
Communication
Port
DR No.
Data Register Function
Data Register Value Updated
R/W
Port 1 to Port 3
D8104
Control signal status
Every scan
R
D8105
DSR input control signal option
When sending/receiving data
R/W
D8106
DTR output control signal option
When sending/receiving data
R/W
Bit 15
0
2
0
1
0
0
D8104
0
3
Port 1
Port 2
0
4
0
5
Port 3
D8104 2-bit Binary Value
DTR
DSR
Description
00
OFF
OFF
Both DSR and DTR are off
01
OFF
ON
DSR is on
10
ON
OFF
DTR is on
11
ON
ON
Both DSR and DTR are on
Communication
Mode
D8105
3-bit Binary Value
DSR (Input) Status
RUN Mode
STOP Mode
User
Communication
Mode
000 (default)
No effect
No effect (TXD/RXD disabled)
001
ON:
OFF:
Enable TXD/RXD
Disable TXD/RXD
No effect (TXD/RXD disabled)
010
ON:
OFF:
Disable TXD/RXD
Enable TXD/RXD
No effect (TXD/RXD disabled)
011
ON:
OFF:
Enable TXD
Disable TXD
No effect (TXD/RXD disabled)
100
ON:
OFF:
Disable TXD
Enable TXD
No effect (TXD/RXD disabled)
≥
101
No effect
No effect (TXD/RXD disabled)
Maintenance Mode
—
No effect
No effect
Communication
Mode
D8106
2-bit Binary Value
DTR (Output) Status
RUN Mode
STOP Mode
User
Communication
Mode
00 (default)
ON
OFF
01
OFF
OFF
10
RXD enabled:
RXD disabled:
ON
OFF
OFF
11
ON
OFF
Maintenance Mode
—
ON
ON
Содержание MICROSmart FC6A-C16K1CE
Страница 1: ...B 1730 2 FC6A SERIES All in One Type Communication Manual...
Страница 60: ...3 COMMUNICATION SETTINGS 3 22 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 76: ...4 MAINTENANCE COMMUNICATION 4 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 126: ...5 USER COMMUNICATION INSTRUCTIONS 5 50 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 158: ...6 MODBUS COMMUNICATION 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 200: ...8 J1939 COMMUNICATION 8 32 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 218: ...10 SEND E MAIL FUNCTION 10 16 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730...
Страница 252: ...INDEX 4 FC6A SERIES MICROSMART ALL IN ONE TYPE COMMUNICATION MANUAL FC9Y B1730 INDEX...