24
‐
13
Troubles
at
System
Start
‐
up
The
following
table
summarizes
possible
troubles
at
system
start
‐
up,
probable
causes
and
actions
to
be
taken.
Trouble
Cause
and
Action
PWR
LED
is
off.
(power)
AS
‐
Interface
power
is
not
supplied
to
the
AS
‐
Interface
master
module.
Check
that
wiring
is
correct
and
AS
‐
Interface
power
is
supplied.
Power
is
not
supplied
from
the
CPU
module
to
the
AS
‐
Interface
master
module.
Check
the
connection
between
the
CPU
module
and
the
AS
‐
Interface
master
module.
FLT
LED
is
on.
(fault)
Slave
configuration
on
the
bus
is
incorrect.
Use
the
WindLDR
slave
monitor
function
to
check
that
slaves
are
connected
correctly.
Perform
configuration,
if
necessary.
For
the
con
‐
figuration
method,
see
If
FLT
LED
remains
on
even
though
slaves
are
connected
correctly
and
configuration
is
com
‐
pleted,
either
disconnect
and
reconnect
the
AS
‐
Interface
connector,
or
turn
off
and
on
the
AS
‐
Interface
power
supply.
LMO
LED
is
on.
(local
mode)
The
CPU
module
fails
to
communicate
with
the
AS
‐
Interface
master
module.
Check
the
fol
‐
lowing
points.
Is
the
CPU
module
compatible
with
AS
‐
Interface?
Check
the
Type
No.
of
the
CPU
module.
Is
a
check
mark
put
in
the
check
box
“Use
AS
‐
Interface
Master
Module”
in
WindLDR
Func
‐
tion
Area
Settings?
The
box
is
checked
as
default.
If
not,
put
a
check
mark
and
download
the
user
program
to
the
CPU
module.
OFF
LED
is
on.
(offline)
While
a
slave
of
address
0
was
connected,
power
was
turned
on.
After
changing
the
slave
address,
power
up
again.
For
the
address
changing
method,
see
35.
Slave
operation
is
unstable.
Check
if
there
are
two
or
more
slaves
with
the
same
address.
Each
slave
must
have
a
unique
address.
If
two
slaves
have
the
same
address
and
same
identification
codes
(ID,
I/O,
ID2,
ID1),
the
AS
‐
Interface
master
module
may
fail
to
detect
an
error.
When
changing
the
dupli
‐
cate
slave
address
using
WindLDR,
remove
one
of
the
slaves
from
the
bus.
Содержание MICROSmart FC5A Series
Страница 1: ...FC5A SERIES FC9Y B1273 1 User s Manual Advanced Volume ...
Страница 2: ......
Страница 8: ...Preface 6 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 14: ...TABLE OF CONTENTS vi FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 52: ...4 DATA COMPARISON INSTRUCTIONS 4 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 72: ...5 Binary Arithmetic Instructions 5 20 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 88: ...7 SHIFT ROTATE INSTRUCTIONS 7 12 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 112: ...8 DATA CONVERSION INSTRUCTIONS 8 24 FC5A MicroSmart User s Manual FC9Y B1273 ...
Страница 138: ...11 PROGRAM BRANCHING INSTRUCTIONS 11 14 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 178: ...13 PULSE INSTRUCTIONS 13 32 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 202: ...14 PID INSTRUCTION 14 24 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 206: ...15 DUAL TEACHING TIMER INSTRUCTIONS 15 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 214: ...16 INTELLIGENT MODULE ACCESS INSTRUCTIONS 16 8 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 248: ...21 COMPUTER LINK COMMUNICATION 21 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 272: ...23 MODBUS TCP COMMUNICATION 23 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 332: ...25 EXPANSION RS232C RS485 COMMUNICATION 25 16 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 341: ...NOTE FC5A MICROSMART USER S MANUAL FC9Y B1273 1 ...
Страница 342: ...NOTE 2 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...