5 User Communication
3-74
WindO/I-NV4 User’s Manual
BCC (Block Check Code)
The BCC comparison data is automatically calculated from the receive data and compared with the BCC part of the
receive data.
This can be configured only when
RXD
is selected as
Type
on the Command Settings dialog box, and
BCC
is selected
under
Type
on the Data Settings dialog box.
■
Calculation Start Position
Specify the position (1 to 15) in the receive data where BCC calculation starts. The position is counted backwards,
with the first position of the receive data taken as 1.
■
Calculation End Position
Specify the position (0 to 15) in the receive data where BCC calculation ends. The position is counted forwards, with
the data position before the BCC taken as 0.
■
Calculation Type
Select the method to calculate the data between the Calculation Start Position and Calculation End Position.
1
(31h)
4
(34h)
5
(35h)
2
(32h)
STX
(02h)
3
(33h)
BCC
CR
(0Dh)
(1)
(2)
(3)
(4)
(5)
(6)
Calculation Start Position:
Receive data:
1
(31h)
4
(34h)
5
(35h)
2
(32h)
STX
(02h)
3
(33h)
BCC
CR
(0Dh)
(5)
(4)
(3)
(2)
(1)
(0)
Calculation End Position:
Receive data:
XOR:
Calculates the data with exclusive logical add.
ADD:
Calculates the data using addition.
ADD (2's Complement): Calculates the data using addition, inverts the bit and adds one.
Modbus ASCII (LCR):
Calculation is performed according to the following procedure. Conversion Type:
Hexadecimal to ASCII, Number of bytes: 2
1. Convert the ASCII characters between Calculation Start Position and Calculation End
Position into 1-byte hexadecimal data for each set of two characters.
Example: 37h, 35h
→
75h
2. Calculate the sum of the data obtained in step 1.
3. Invert the bit of the result of step 2 and add one. (2’s complement)
4. Convert the lower one byte data of the result of step 3 into ASCII characters.
Example: 75h
→
37h, 35h
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...