4 E-mail Function
28-42
WindO/I-NV4 User’s Manual
4.6 Operating E-mail function and checking sending status
●
Operating E-mail function
Enables to cancel or pause the e-mail sending by the HMI Special Internal Relay.
■
LSM55: Cancelling the e-mail sending
When a value of this bit changes from 0 to 1, the MICRO/I cancels sending of all the e-mails in "Waiting" status. If
sending an e-mail is in progress, the send process will be cancelled after such e-mail has been sent.
■
LSM56: Pausing the e-mail sending
While a value of this bit is 1, the MICRO/I pauses sending of all the e-mails in "Waiting" status. If sending an e-mail is
in progress, the send process will be paused after such e-mail has been sent.
●
Checking the e-mail sending state
You can check the e-mail sending state through the values of the HMI Special Data Register.
■
LSD221: Number of e-mail in "Waiting" status
The number of e-mail that are waiting to be sent is stored.
■
LSD222: Result of e-mail sending
The sending result of the e-mail last sent is stored.
■
LSD223: E-mail Number which has been sent
The e-mail number which has been sent is stored. Only the latest e-mail number is stored.
Parameter
Cause
0:
Successfully Completed
-
1:
Parameter error
• The value of the device address allocated to the following setting is 0
- IP address of the Outgoing mail server (SMTP)
- Sender E-mail Address
- Sender Name
- Account Name and Password (When the Required authentication (LOGIN)
to send E-mail check box is selected)
• The preferred DNS server and alternate DNS server settings remain the
default settings.
2:
Timeout error
• An Ethernet cable is disconnected.
• Host Name of the Outgoing mail server (SMTP) is incorrect.
• IP address of the Outgoing mail server (SMTP) is incorrect.
• Port number of the Outgoing mail server (SMTP) is incorrect.
• A connection cannot be made to the preferred DNS server and alternate DNS
server.
3:
Authentication error
• The authenticating account name is incorrect.
• The authenticating account password is incorrect.
4:
None of the above
The connection is disconnected from the outgoing mail server (SMTP).
After the value of the device address specified in the
Report when E-mail has been sent
on the
Settings
dialog box changes to 1, the result of the e-mail sending is stored in LSD222.
Even when an error occurs during sending, the MICRO/I handles the send process is completed and the e-
mail number is stored in LSD223.
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...