WindO/I-NV4 User’s Manual
3-3
2 O/I Link Communication
3
Communic
ation
2.1 Overview
O/I Link Communication is a protocol for communication between Master and Slave, where a MICRO/I connected to
the external device is configured as a Master and multiple MICRO/I (Slaves) communicate with the external device via
the Master.
The Master MICRO/I unit communicates with the external device by means of Device Link Communication. The
Master MICRO/I is called an O/I Link Master and a slave MICRO/I connected to the O/I Link Master is called an O/I
Link Slave. A maximum of 15 O/I Link Slaves can be connected to an O/I Link Master.
2.2 O/I Link Communication Settings
These settings are configured under the
O/I Link
tab on the Project Settings dialog box. The Project Settings dialog
box can also be accessed using the following methods.
• Click
Project
on the
Configuration
tab.
• Double click
Project Settings
in the
Project
window.
The O/I Link Communication Settings can only be configured when
O/I Link Master
or
O/I Link Slave
is selected
in
Function
under
Interface Settings
on the
Communication Interface
tab. For details, refer to Chapter 4 “3.5
2
O/I Link Communication
HG3G
HG2G-5F
HG5G-V HG4G-V
HG3G-V
HG2G-V
HG2G-5T
HG4G
HG1G HG1P
Read
Write
5678
MICRO/I
O/I Link Slave
(Slave 1)
MICRO/I
O/I Link Slave
(Slave 2)
MICRO/I
O/I Link Slave
(Slave 15)
MICRO/I
O/I Link Master
External device
0
1
Read
Write
D1:
M1:
5678
O/I Link Communication
Device Link Communication
Numerical Display
Reference Device Address: D1
Bit Button
Destination Device Address: M1
Read
Write
Read
Write
O/I Link Communication can only be used for the
External Device Communication 1
. The
communication driver of O/I Link Slave should match the O/I Link Master's.
For details regarding the O/I Link Communication, refer to Chapter 3 "O/I Link Communication" in the
WindO/I-NV4 External Device Setup Manual.
• Use the runtime system version 4.01 or later when connecting the HG5G/4G/3G/2G-V, HG4G/3G, HG2G-
5F/-5S/-S, HG1G/1P via O/I Link Communication.
• The HG5G/4G/3G/2G-V, HG4G/3G, HG2G-5F/-5T, HG1G/1P and the HG4F/3F/2F/2S/1F use a different
protocol for the O/I Link Communication. To communicate them via the O/I Link Communication, select
the
Use the same O/I Link Communication as the HG4F/3F/2F/2S/1F
check box on the
Compatible
tab of the
Project Settings
dialog box.
Содержание MICRO/I HG4G-CJT22 F-B Series
Страница 1: ...B 1701 11 User s Manual ...
Страница 26: ...Preface 25 WindO I NV4 User s Manual ...
Страница 50: ...1 WindO I NV4 Specifications 2 18 WindO I NV4 User s Manual Baltic Font ANSI 1257 Cyrillic Font ANSI 1251 ...
Страница 106: ...5 WindO I NV4 Common Operations and Settings 2 74 WindO I NV4 User s Manual ...
Страница 254: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual ...
Страница 362: ...5 Screen Restrictions 5 28 WindO I NV4 User s Manual ...
Страница 402: ...3 Text 7 30 WindO I NV4 User s Manual ...
Страница 574: ...9 Potentiometer 8 172 WindO I NV4 User s Manual ...
Страница 1052: ...4 Using the Data 15 22 WindO I NV4 User s Manual ...
Страница 1170: ...6 Important Notes 20 60 WindO I NV4 User s Manual ...
Страница 1200: ...5 Restrictions 22 18 WindO I NV4 User s Manual ...
Страница 1260: ...5 Editing User Accounts on the MICRO I 23 60 WindO I NV4 User s Manual ...
Страница 1286: ...4 Clear 24 26 WindO I NV4 User s Manual 4 Click Yes 5 Click Close This concludes clearing data ...
Страница 1288: ...4 Clear 24 28 WindO I NV4 User s Manual 6 Click Yes 7 Click Close This concludes clearing data on the external memory device ...
Страница 1322: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual ...
Страница 1414: ...4 E mail Function 28 66 WindO I NV4 User s Manual ...
Страница 1554: ...3 Settings 34 14 WindO I NV4 User s Manual ...
Страница 1642: ...2 Handling Problems 36 6 WindO I NV4 User s Manual ...
Страница 1652: ...5 Text Alignment A 10 WindO I NV4 User s Manual ...
Страница 1664: ...Index 12 WindO I NV4 User s Manual ...