Technical Data
HR9Z-B2200 8/2020
31
Data Functional Safety
Data Functional Safety
Characteristic
Value
Defined safe state
Safety-related outputs are de-energized
Normally Open: open
Normally Closed: closed
Maximum Performance Level (PL), Category
(as per ISO 13849-1:2015)
Normally Open: PL e, Category 4
Normally Closed: PL c, Category 1
Actual PL and category depend on wiring and
configuration.
Maximum Safety Integrity Level (SIL)
(as per IEC 61508-1:2010)
Normally Open: 3
Normally Closed: 1
Actual SIL depends on wiring and configuration.
Safety Integrity Level Claim Limit (SILCL)
(as per IEC 62061:2005+AMD1:2012+AMD2:2015)
Normally Open: 3
Normally Closed: 1
Actual SILCL depends on wiring and configuration.
Type
(as per IEC 61508-2)
B
Hardware Fault Tolerance (HFT)
(as per IEC 61508 and IEC 62061)
1
Stop Category for Emergency Stops
(as per ISO 13850 and IEC 60204-1)
0
Lifetime in years at an ambient temperature of 55 °C (131 °F)
(1)
(as per IEC 61508)
20
Safe Failure Fraction (SFF)
(as per IEC 61508 and IEC 62061)
>99 %
Probability of Dangerous Failure per hour (PFH
D
) in 1/h
(as per IEC 61508 and ISO 13849-1)
0.88 x 10
-9
Mean Time To Dangerous Failure (MTTF
D
) in years
(high as per ISO 13849-1)
>30
Average Diagnostic Coverage (DC
avg
)
(high as per ISO 13849-1)
≥99 %
Maximum number of cycles over lifetime
DC-13, 24 VDC 1 A: 1,200,000
DC-13, 24 VDC 3 A: 275,000
AC-1, 250 VAC 4 A: 90,000
AC-15, 250 VAC 1 A: 90,000
AC-15, 250 VAC 3 A: 60,000
(1)
With 24 VAC supply, the lifetime value of 20 years applies at an ambient temperature of 50 °C (122 °F).
Содержание HR6S-DN
Страница 1: ...http www idec com HR6S DN Safety Module Original instructions HR9Z B2200...
Страница 8: ...8 HR9Z B2200 8 2020...
Страница 14: ...14 HR9Z B2200 8 2020...
Страница 20: ...Introduction 20 HR9Z B2200 8 2020...
Страница 56: ...Installation 56 HR9Z B2200 8 2020...
Страница 60: ...Functions 60 HR9Z B2200 8 2020 Wiring of the inputs for Emergency Stop Wiring of the inputs for guards...
Страница 64: ...Functions 64 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 66: ...Functions 66 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Страница 69: ...Functions HR9Z B2200 8 2020 69 Wiring of the inputs for sensors devices with two PNP outputs...
Страница 72: ...Functions 72 HR9Z B2200 8 2020 Wiring of the inputs for sensors devices with OSSD outputs...
Страница 98: ...Accessories Service Maintenance and Disposal 98 HR9Z B2200 8 2020...