26: C
OMPUTER
L
INK
C
OMMUNICATION
26-2
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
Programming WindLDR
In the 1:1 computer link system, a computer can be connected to either port 1 or 2 on the
MicroSmart
CPU module. In the
1:N computer link system, a computer must be connected to port 2 on the CPU module and every CPU module must have
a unique device number 0 through 31. The Communication page in the Function Area Settings must be programmed for
each station in the computer link system. If required, communication parameters can also be changed.
Since these settings relate to the user program, the user program must be downloaded to the
MicroSmart
after changing
any of these settings.
1.
From the
WindLDR
menu bar, select
Configure
>
Function Area Settings
. The Function Area Setting dialog box
appears.
2.
Click the
Communication
tab, and select
Maintenance Protocol
in the Port 1 or 2 pull-down list.
3.
Click the
Configure
button. The Communication Parameters dialog box appears. Change settings, if required.
4.
Click the
OK
button.
Baud Rate (bps)
1200, 2400, 4800, 9600, 19200
Data Bits
7 or 8
Parity
None, Odd, Even
Stop Bits
1 or 2
Receive Timeout (ms)
10 to 2540 (10-msec increments)
(Receive timeout is disabled when 2550
is selected.)
Device Number
0 to 31
Mode Selection Input
Any input number
Note:
Only when the mode selection input is turned on, the selected communication parameters are enabled.
Other wise, default communication parameters take effect; 9600 bps, 7 data bits, even parity, 1 stop bit,
receive timeout 500 msec.
Содержание FC4A-C10R2
Страница 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Страница 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Страница 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Страница 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Страница 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Страница 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Страница 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Страница 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Страница 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Страница 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Страница 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Страница 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Страница 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...