background image

1. CONNECTOR RATINGS

2. TOOLING CHART

3. REDUCING BUSHING

SBE

®

 & SBX

®

 Connectors

Assembly instruction for SBE160, SBE320, SBX175 and SBX350 Series

two pole battery connectors with option for auxiliary contacts.

FOR INSTALLATION BY A QUALIFIED ELECTRICIAN IN 

ACCOR

DANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES 

AND THE FOLLOWING INSTRUCTIONS.  THE SUITABILITY OF THIS 

TYPE OF TERMINATION MUST BE EVALUATED BY UNDERWRITERS’ 

LABORATORIES, INC. AND CANADIAN STANDARDS.  ASSOCIATION 

FOR THE END USE APPLICATION: Assemble contacts to the cables 

according to the equipment manufacturer’s assembly instructions. The 

following instructions are supplied as a reference. Please note: instruc-

tions are included with each crimp tool for proper use.

CAUTION: When using cable with jacket diameter less 

than 0.423 inches (11mm) on the SBE160 / SBX175 and 

less than 0.709 inches (18mm) on the SBE320 / SBX350 

thin wall heat shrink insulation should be evenly applied 

across the cable and contact barrel junction to insure 

finger protection.

Contains one (1) housing and two (2) contacts.

    

Max Cable Size

Series  Amperes  Volts  AWG     mm²

SBE160 160 

150  1/0 

50

SBE320  320 

150  300mcm 150

SBX175 175 

600  1/0 

50

SBX350  350 

600  300mcm 150

Bushing 

Wire Size 

For Use With 

 

Part Number  AWG (mm²)  SBE160 / SBX175   SBE320 / SBX350

5687 

#1 (42.4) 

6384G1 contact 

6354 c 5918 bushing

5690 

#2 (33.6) 

6384G1 contact 

6354 c 5918 bushing

5693 

#4 (21.2) 

6384G1 contact 

6354 c 5918 bushing

5663 

#6 (13.3) 

6384G1 contact 

6354 c 5918 bushing

5648 

#10 (5.3) 

6384G1 contact 

6354 c 5918 bushing

5920 

N/A (16) 

6384G2 contact 

6394 contact

5918 

1/0 (53.5) 

N/A 

6354 contact

Contact 

Wire 

Pneumatic  

 

  Dieless 

Part Number  Size 

Bench Tool  + Die   +  Locator  or  Hydraulic Tool

6384G2 

35 mm² 

1387G1 

1388G3  1389G3

6384G1 

1/0 AWG 

1387G2 

1303G2  1304G2

6354 

2/0 AWG 

1387G1 

1388G2  1389G2

6354 

2/0 AWG 

1387G2 

1303G12  1304G28

6355 

3/0 AWG 

TBD 

TBD 

TBD

6356 

4/0 AWG 

TBD 

TBD 

TBD 

6358 

300 MCM 

TBD 

TBD 

TBD 

   

1341G1 

50 mm² 

1387G2 

1303G8  1304G27 

   

1341G2 

70 mm² 

1387G2 

1303G7  1304G27 

1341G3 

95 mm² 

TBD 

TBD 

TBD

HEAT SHRINK INSULATION SPECIFICATIONS

Connector  Nominal 

Minimum Maximum

Series 

Tubing Size 

Length 

Wall Thickness

SBE320 / SBX350 

0.75 in (19mm) 

2.0 in (51mm)  0.030 in (.76mm)

SBE160 / SBX175 

0.50 in (12.7mm) 

2.0 in (51mm)  0.025 in (.63mm)

1368

1368

1368

1368

1368

1368

1368

1368

1368

1368

[19.0]  0.75 MIN

[3.2]  0.12 MIN

[3.2]  0.12 MIN

Отзывы: