INSTALLATION
16
Buccaneer GT Range
- Installation
10 PERFORMANCE DATA
CHARACTERISTICS TABLE
Boiler Size
3
4
5
Maximum Heat Output
kW
26
33
40
Btu/h x 10
3
88
112
136
Minimum Heat Output
kW
16
26
33
Btu/h x 10
3
55
88
112
Combustion Chamber Volume
m
3
0.016
0.02
0.025
ft
3
0.56
0.74
0.9
Flue Way Volume
m
3
0.03
0.04
0.05
ft
3
1.09
1.45
1.8
Boiler Water Content
l
19
24.5
30
gal
4.18
5.4
6.6
Hydraulic Resistance at 15k
mbar
1.7
2.8
4.1
in.w.g.
0.68
1.12
1.64
Combustion Chamber Resistance
mbar
0.05
0.05
0.05
in.w.g.
0.02
0.02
0.02
Minimum Draught at Smokehood outlet
mbar
0.15
0.2
0.2
(for max output)
in.w.g.
0.06
0.08
0.08
Boiler DRY weight less burner unit
kg
121
149
177
lb
267
328
390
General Data
Boiler Size
3
4
5
Maximum Oil Rate
l/h
2.67
3.4
4.12
gal/h
0.59
0.75
0.91
Maximum Flue gas volume
l/sec
16.7
21.2
25.7
ft
3
/min
35.4
45
54.6
Oil Firing Data
Boiler Size
3
4
5
Maximum Gas Rate
m
3
/h
2.7
3.4
4.2
ft
3
/h
95.3
120
148
Maximum Flue gas volume
m
3
/sec
0.015
0.02
0.023
ft
3
/min
31.7
42.4
48.7
Gas Firing Data
Data Notes:
Fuel rates and flue gas data relates to maximum outputs
ratings Gas firing data relates to the use of NATURAL GAS
ONLY Details for the use of LPG are available, on request, to
Caradon Ideal Ltd. The gas rate at calorific values differing
from the standard quoted above may be calculated by direct
proportion CALORIFIC VALUE; 38.5 MJ/m
3
(1035 btu/ft
3
)