UL and ULC Installation Requirements
Only UL / ULC listed compatible products are intended to be connected to a UL / ULC listed control system.
CAN/ULC-S319
⦁
This card reader is CAN/ULC-S319 Listed for Class I applications only.
⦁
Exit devices and wiring must be installed within the protected area.
⦁
The card reader must be connected with shielded, grounded cable.
⦁
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
⦁
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to ULC-S533 and
CAN/ULC-S104.
⦁
Must be installed with CAN/ULC-S319 Listed portal locking device(s) for ULC installations.
⦁
Input power must be supplied by a Class 2 or power limited device.
UL 294
⦁
This card reader is UL 294 Listed for Class 1 applications only.
⦁
Exit devices and wiring must be installed within the protected area.
⦁
The card reader must be connected with shielded, grounded cable.
⦁
Fail secure locking mechanism shall only be installed where allowed by the local authority having jurisdiction
(AHJ) and shall not impair the operation of panic hardware and emergency egress.
⦁
If fire resistance is required for door assembly, portal locking device(s) must be evaluated to UL10B or
UL10C.
⦁
Must be installed with UL 1034 Listed electronic locks for UL installations.
⦁
Input power must be supplied by a Class 2 or power limited device.
⦁
A means of verification shall be employed by the user to enable access to the wireless electronic device
such as a PIN or biometric feature, which subsequently provides access to the credential application
software present on the wireless electronic device.
⦁
The access control system shall have the means to distinguish between the type of credential used via code
or description (e.g. authentication/digital signature keys received from a physical card vs.
authentication/digital signature keys received from a wireless electronic credential.)
Performance Levels
Destructive Attack Line Security
Endurance
Standby Power
tSec Standard Reader Level I
Level I when wired with Wiegand
Level IV when wired with RS485
Level IV
Level I
tSec Mini Reader
Level I
Level I when wired with Wiegand
Level IV when wired with RS485
Level IV
Level I
tSec Extra Reader
Level I
Level I when wired with Wiegand
Level IV when wired with RS485
Level IV
Level I
PRX-TSEC Range | tSec Multi-Technology Card Reader with Bluetooth® Technology | Installation Manual