Battery Indicator
The battery indicator shows the status of the backup battery.
State
Description (with mains power connected - power indicator on)
Flashing (red)
Backup battery is disconnected
On (red)
Backup battery failed its dynamic battery test
On (green)
Last backup battery dynamic test successful
State
Description (with mains power disconnected - power indicator off)
Flashing (red)
Mains has failed and the PSU is drawing power from the battery. State is Battery Low
Flashing (green) Mains has failed and the PSU is drawing power from the battery. State is Battery Restore
Temp Indicator
The temp indicator will show the status of the unit's core temperature.
State
Description
On (red)
Core temperature exceeded.
Over Temp Shutdown Activated
Flashing (red)
Core temperature within 15˚C of over temp shutdown
On (green)
Core temperature OK
Over Current Indicator
The over current indicator will show the status of the output current for both V1+ and V2+.
State
Description
On (red)
Output current exceeded.
Over Current Shutdown Activated
Off
Maximum output current not exceeded
PRT-PSU-DIN-2A | Protege DIN Rail 2A Intelligent Power Supply | Installation Manual