3.2.5 Alarm History
The Alarm History screen displays a log of the 20 most recent alarm events.
These alarms may have been raised by any module experiencing an alarm,
or by one of the four external Alarm Inputs being triggered.
Other information will be shown depending on the operating state of the unit:
•
If there is no alarm history, the screen will display No Alarms in History
and the Alarm History log screen will not be displayed.
Alarm History screen if no alarms in history
Alarm History screen with alarms in history
Press Enter to see Alarm History log.
Scroll through the history screens to see the
20 most recent Alarm events. Shows the
module that raised the alarm, date, and time
when set, and cleared.
NOTE: The system date and time are normally set by the network. These
may be manually set, see GUI, Communications Basic Setup tab
(see Section 4.7.1).
3.2.6 Network Status and Advanced Options
The Network Status screen displays the network connectivity, "IP address"
of the system, and the assigned MAC address.
Press Enter to move to the Advanced Options screen.