ICT STANDARD DUAL BUS DISTRIBUTION PANELS 

The  ICT  Dual  Bus  Distribution  Panel  provides  two  100A  (peak) 
bus  inputs  with  six  independent  output  channels  per  bus  in  a 
compact  1U  high  chassis  for  19  inch  rack  mounting.  Over 
current  protection  for  each  output  is  available  on  the  front 
panel in two configurations; with 80VDC rated blade style fuses, 
or  with  65VDC  user  insertable  magnetic-hydraulic  circuit 
breakers. 
 
Each  bus  can  accommodate  a  supply  voltage  from  10VDC  to 
60VDC,  either  positive  or  negative  polarity,  with  a  peak  input 
current of 100A to be  distributed at 25A maximum on  each of 
the  6  output  channels.  Each  channel  has  independent  over 
current protection. 
 
Fuse  status  is  displayed  by  an  LED  indicator  located  over  each 
fuse, while breaker trip status is indicated locally by the rocker 
handle  position.  Form-C  alarm  output  contacts  (C/NO/NC)  are 
provided  on  the  back  panel  for  each  bus  to  indicate  that  a 
channel fuse or breaker has opened.  
 
Model Numbers: (covered in this manual) 

ICT200DF-12

 

Standard Dual 100A Bus Fuse Distribution 
Panel for +/- 12, 24 or 48VDC 

ICT200DB-12

 

Standard Dual 100A Bus Breaker 
Distribution Panel for +/-12, 24 or 48VDC 

 

  WARNING

 

Risk of serious personal injury or damage to equipment and 
property! Always observe the following: 

 

Use an appropriately rated over-current protection device 
and disconnect switch in line with the main battery 
connections  to the panel  

 

Shut off or disconnect all dc power sources before 
connecting or disconnecting any wiring 

 

Use wire and connectors rated for the maximum load 
current  and size of fuse or circuit breaker, and keep cable 
lengths as short as practical 

 

Carefully observe wiring polarity when making input and 
output connections 

 

Securely tighten all connections  

 

CAUTION 

Risk of personal injury or damage to equipment! Always 
observe the following: 

 

Install unit in a restricted access location (such as 
equipment rack) to limit unintentional contact with 
terminals and wiring 

 

Ensure the total power consumption of the loads does not 
exceed the 100A (peak), 80A (continuous) rated capacity of 
each power bus 

 

Ensure load current through each output channel does not 
exceed  25A maximum, or 20A continuous 

 

Do not block air inlet or outlet openings in the panel sides

 

 

INSTALLATION 

Inspect your distribution panel to ensure it was not damaged in 
shipping, and has all accessories: 

 

4 black plastic boots to insulate main dc power 
connections (shipped with unit) 

 

4 M8 size nut/washer/split-washer sets for high 
current bus connector studs (shipped on unit) 

 

2 three pin alarm output connector plugs (shipped on 
unit) 

 

8 ICT-BLP Breaker blanking plugs (ICT200DB-12 only) 

 
To  complete  the  installation  you  will  also  need  appropriate 
fuses (FKS-ATO type) or circuit breakers (available from ICT) for 
each  distribution  channel  you  plan  to  use.  Twelve  15A  80VDC 
FKS-ATO blade fuses are shipped with each ICT200DF-12 panel, 
while  circuit  breakers  need  to  be  ordered  separately  from  ICT 
per the following list for use on the ICT200DB-12 panel: 

 

Breakers: 

ICT 
Model 

Rating 
(65VDC) 

Mfg. Part Number 

ICT-CB5 

5A 

Carling MA1-B-14-450-1-A26-2-J  

ICT-CB10 

10A 

Carling MA1-B-14-610-1-A26-2-J  

ICT-CB15 

15A 

Carling MA1-B-14-615-1-A26-2-J  

ICT-CB25 

25A 

Carling MA1-B-14-625-1-A26-2-J  

CBI rocker handle circuit breakers with 0.25” tab terminals and 
current ratings up to 25A may also be used, consult ICT for 
suitable part numbers. 

 

Fuses: 

ICT Model 

Rating 
(80V) 

Mfg. Part Number 

ICT- 80VF15 

15A 

Little Fuse FKS-ATO, 166.7000.5156 

For 12V and 24V systems standard 32VDC ATO style blade fuses 
may  be  used,  with  current  ratings  up  to  25A.  These  fuses  are 
widely available from multiple manufacturers. 
 
Mount the Dual Bus  Distribution Panel in a 19 inch equipment 
rack, using standard rack mounting hardware. (Not provided) 
 
On  breaker  equipped  models  install  appropriately  rated  circuit 
breakers  and  blanking  plugs  in  desired  channel  locations  by 
carefully inserting a  breaker so that its mounting  tabs  securely 

snap  into  the  front  panel.  Breakers  are  not  removable  once 
inserted.  
On  fuse  equipped  units  change  any  channel  fuses  requiring 
different current ratings. (Up to 25A max) 
 
Bond the panel chassis to the rack system ground, connecting a 
ground wire with ring tongue to the back panel ground stud. (8-
32 thread) 
 
Connect Bus A loads to each output channel using suitable wire 
(10AWG  max)  sized  for  the  fuse  or  breaker  installed  on  the 
channel, stripping 10-11mm of insulation and firmly clamping in 
the  Bus  A  channel  1  to  6  output  connectors  by  tightening  the 
clamping screw.  Note which load is connected to each channel, 
for future reference. 
 
Repeat  for  the  Bus  B  loads  if  required.  The  unit  may  be 
operated with either Bus A or Bus B powered, or both. 
 

NOTE! 

All  channel  RTN  lines,  and  the  main  high  power  Bus  A  and  Bus  B 
RTN terminals are common, and tied to a single internal Return bus. 
Bus A and Bus B inputs can be wired to a different dc voltage (10 to 
60Vdc)  of  either  polarity,  but  must  share  a  common  RTN  voltage, 
normally at earth potential. 

It may be possible to measure a voltage on the output terminal(s) 
even  if  the  breaker  or  fuse  is  open.  This  is  normal  operation.  The 
high-impedance  detection  circuitry  may  report  a  voltage  reading 
that is purely a signal voltage and does not support loading.   

 
Connect  the  main  Bus  A  RTN  line  to  the  external  battery  or 
power supply return using wire and ring connectors rated for up 
to  100A  continuous  current.  Feed  the  wire  through  the  plastic 
insulating cap (supplied), and connect the ring tongue to the M8 

RTN

 stud, then securely fasten with supplied hardware. Slip the 

insulating  cap  over  the  high  current  ring  tongue  and 

RTN

  stud 

on  the  back  panel  to  help  prevent  accidental  contact  with  the 
stud connection. 
 
Connect  the  Bus  A  Input  through  a  suitably  rated  disconnect 
switch  (

set  in  the  open  position

)

 

and  a  fuse  or  circuit  breaker 

rated  for  100A  max  continuous  operation  to  the  external 
battery  or  power  supply  output,  using  wire  and  connectors 
rated  for  100A  continuous  current.  Feed  the  wire  through  the 
plastic  insulating  cap  (supplied),  and  connect  the  input  ring 
tongue  to  the  M8 

Bus  A  Input

  stud,  then  securely  fasten  with 

supplied  hardware  and  slip  the  cap  over  the  ring  tongue  and 
stud  to  help  prevent  accidental  contact  with  the  input  stud 
connection. 
 
Repeat input wiring for the Bus B input, its power source and 
over current protection device, if the Bus B outputs are to be 