Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
52
of 84
Table 28. Deeply discharged battery values (typical)
24 VDC Units
48 VDC Units
20 VDC
40 VDC
Battery Over-Current Alarm
Over-Current Threshold:
Set the threshold to receive an alarm
notification when the battery discharge or charge current exceeds a set
overcurrent level. Set the threshold to 0 amps to disable this alarm. The
default setting is 0 (Disabled).
Battery Low SOC Alarm
SOC Threshold
: Set this to receive an alarm notification when the
battery state of charge falls below the specified level. Set the threshold
to 0 amps to disable this alarm. This setting is only available if the system
is configured for use with a lead-acid type battery. The default setting is
0 (Disabled).
Alarm Reporting
Ignore Circuit Breaker 2 Status
: Select the check box to prevent alarm
e-mails being sent when a single battery is connected to a BMMD. This
setting is only available if a BMMD is installed. The default setting is
Disabled.
Activate Alarm Form C Contact:
Select the check box to have the rear
panel alarm contacts change state for an alarm condition. The default
setting is Enabled.