background image

16

Specifications subject to change without notice.

516 01 3604 04

NOTE: TEST LEADS — Unit may be equipped with short

test  leads  (pigtails)  on  the  field  line  connection  points  on

contactor C or optional disconnect switch. These leads are

for factory-run test purposes only; remove and discard be

-

fore connecting field power wires to unit connection points.

Make  field  power  connections  directly  to  line  connection

pressure lugs only.

    

Fig. 27 — Disconnect Switch and Unit

ALL UNITS
All field wiring must comply with NEC and all local codes.

Size  wire based on MCA (Minimum  Circuit Amps) on the

unit informative plate. See Fig. 26 and the unit label diagram

for  power  wiring  connections  to  the  unit  power  terminal

blocks and equipment ground. Maximum wire size is #2/0

AWG (copper only) per pole.

Provide a ground fault and short circuit over-current protec

-

tion device (fuse or breaker) per NEC Article 440 (or local

codes). Refer to unit informative data plate for MOCP (Max

-

imum Over-Current Protection) device size.

Voltage to compressor terminals during operation must be

within  voltage  range  indicated  on  unit  nameplate.  On

3

-

phase units, voltages between phases must be balanced

within  2%  and  the  current  within  10%.  Use  the  formula

shown in the following example to determine the percent of

voltage imbalance.

Example: Supply voltage is 230-3-60

Determine maximum deviation from average voltage.

(AB) 227-224 = 3 v

(BC) 231-227 = 4 v

(AC) 227-226 = 1 v

Maximum deviation is 4 v.

Determine percent of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maxi

-

mum allowable 2%.

Operation on improper line voltage or excessive phase im

-

balance constitutes abuse and may cause damage to elec

-

trical components. Such operation would invalidate any ap

-

plicable warranty.
UNITS  WITHOUT  FACTORY-INSTALLED  NON-FUSED

DISCONNECT
When installing units, provide a disconnect switch per NEC

(National Electrical Code) of adequate size. Disconnect siz

-

ing data is provided on the unit informative plate. Locate on

unit cabinet or within sight of the unit per national or local

codes. Do not cover unit informative plate if mounting the

disconnect on the unit cabinet.
UNITS  WITH  FACTORY-INSTALLED  NON-FUSED

DISCONNECT 
The factory-installed optional disconnect switch is located in

a  weatherproof  enclosure  located  under  the  main  control

box.  The  manual  switch  handle  is  accessible  through  an

opening in the access panel. Discard the factory test leads

(see Fig. 28). The factory disconnect is 80A disconnect.

WARNING

FIRE HAZARD

Failure to follow this warning could result in personal in

-

jury, death, or property damage.

Do  not  connect  aluminum  wire  between  disconnect

switch and unit. Use only copper wire.

COPPER

WIRE ONLY

ELECTRIC

DISCONNECT

SWITCH

ALUMINUM

WIRE

% Voltage 

Imbalance = 100 x

max voltage deviation from average voltage

average voltage

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

=

227

3

3

% Voltage Imbalance = 100x

4

= 1.78%

227

IMPORTANT: If the supply voltage phase imbalance is more than 2%,

contact your local electric utility company immediately.

A

B

C

MOTOR

Содержание RHH120

Страница 1: ...RING DIAGRAMS Economi er X Factory Option 27 SYSTEM COMPONENTS SPECIFICATIONS INPUTS OUTPUTS ENVIRONMENTAL ECONOMIZER MODULE WIRING DETAILS INTERFACE OVERVIEW ENTHALPY SETTINGS TWO SPEED FAN OPERATION...

Страница 2: ...t DANGER ELECTRICAL SHOCK HAZARD Failure to follow this warning will result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit a...

Страница 3: ...Enthalpy Sensor P 2 Position Damper w Barometric Relief U Ultra Low Leak Economizer w Barometric Relief OA Temp Sensor W Ultra Low Leak Economizer w Barometric Relief Enthalpy Sensor Outdoor Air Optio...

Страница 4: ...4 Specifications subject to change without notice 516 01 3604 04 Fig 2 Unit Dimensional Drawing Size 120 Units...

Страница 5: ...516 01 3604 04 Specifications subject to change without notice 5 Fig 2 Unit Dimensional Drawing Size 120 Units cont...

Страница 6: ...clearances LOCATION DIMENSION CONDITION A 48 in 1219 mm 18 in 457 mm 18 in 457 mm 12 in 305 mm Unit disconnect is mounted on panel No disconnect convenience outlet option Recommended service clearance...

Страница 7: ...o the check valve core s bottom O ring Install the fitting body and torque to 96 10 in lbs 10 9 1 Nm Do not exceed 106 in lbs 11 9 Nm when tightening INSTALLATION Jobsite Survey Complete the following...

Страница 8: ...ing 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounted applications generally follow the sequence for a curb installation Adapt the sequence as required...

Страница 9: ...516 01 3604 04 Specifications subject to change without notice 9 Fig 6 Roof Curb Details REV 50TM500827...

Страница 10: ...t is ready to be rigged and no longer will be lift ed by a fork truck the wood protector under the basepan must be removed Remove 4 screws from each base rail Wood protector will drop to the ground Se...

Страница 11: ...iscard the supply duct cover Install accessory CRDUCTCV001A00 to cover the vertical supply duct open ing Use the return duct cover removed from the unit end panel to cover the vertical return duct ope...

Страница 12: ...own form and assembled to a metal support tray using plastic stretch wrap Located in the return air compartment the assembly s metal tray is at tached to the basepan and also attached to the damper us...

Страница 13: ...e hood sides See Fig 17 and 18 Secure hood divider with 3 screws on each hood side The hood divider is also used as the bottom filter rack for the aluminum filter 5 Attach the post that separates the...

Страница 14: ...must be used to route the main power from the condenser end of the unit to either the factory option disconnect the bottom of the control box or the single point box accessory One inch conduit is pro...

Страница 15: ...1 4 in female spade connector from the 230 v connection and moving it to the 200 v 1 4 in male terminal on the prima ry side of the transformer Refer to unit label diagram for ad ditional information...

Страница 16: ...m deviation is 4 v Determine percent of voltage imbalance This amount of phase imbalance is satisfactory as it is below the maxi mum allowable 2 Operation on improper line voltage or excessive phase i...

Страница 17: ...socket re install 3 hex screws on the NFD enclosure 12 Re install the unit front panel Fig 29 Handle and Shaft Assembly for NFD CONVENIENCE OUTLETS Two types of convenience outlets are offered on RHH...

Страница 18: ...the bottom of the dis connect box For the load side wiring to the factory option disconnect route the wires through the hole on the right side of the disconnect Be sure to create a drip loop at least...

Страница 19: ...conduits Connect the power con duit to the internal disconnect if unit is so equipped or to the external disconnect through unit side panel Remove one of the two knockouts located on the bottom left...

Страница 20: ...ng valve position Reversing valves are ener gized during the cooling stages and the defrost cycle and de energized during heating cycles Once energized at the start of a cooling stage the reversing va...

Страница 21: ...DI 24 vac P2 4 CTB Y2 W1 Heat 1 DI 24 vac P2 7 CTB W1 W2 Heat 2 DI 24 vac P2 6 CTB W2 R Power 24 vac P3 1 CONTL BRD 8 C Common 24 vac P3 2 CONTL BRD 4 DFT 1 DI 24 vac DFT 1 to DFT 1 DFT 2 DI 24 vac D...

Страница 22: ...he bottom left side of the control box after removing one of the two knockouts in the corner of the box Using a connector at the control box to protect the wire as it passes into the control box Pull...

Страница 23: ...can be installed in the unit Use the wir ing procedure listed below for each heater as determined by the number of stages in the heater Single Stage Heaters Single stage heaters will have an orange a...

Страница 24: ...ce 516 01 3604 04 Fig 41 Accessory Electric Heater Control Connections NOTE Optional Outdoor Temperature Control at One Heater Stage Move either heater wire to this terminal and connect outdoor temper...

Страница 25: ...25 Specifications subject to change without notice 516 01 3604 04 Fig 42 Typical RHH Control Wiring Diagram...

Страница 26: ...26 Specifications subject to change without notice 516 01 3604 04 Fig 43 Typical RHH Power Wiring Diagram 208 230 3 60 unit shown...

Страница 27: ...module includes terminals for CO2 sensor Mixed Air sensor and an Outdoor Dry Bulb sensor Enthalpy and other options are available with bus sensors User Interface The interface provides status for norm...

Страница 28: ...040839 001 Rev G HJW10 www energy ca gov Certified FDD Product California Title 24 Part 6 Table 8 Economizer Module Left Hand Terminal Blocks LABEL TYPE DESCRIPTION Top Left Terminal Block MAT MAT 20k...

Страница 29: ...D display and a 4 button keypad on the front of the economizer controller Keypad Use the four navigation buttons see Fig 48 to scroll through the menus and menu items select menu items and to change p...

Страница 30: ...ETUP ADVANCED SETUP CHECKOUT ALARMS NOTE Some parameters in the menus use the letters MA or MAT indicating a mixed air temperature sensor location before the cooling coil This unit application has the...

Страница 31: ..._ F if not connected short or out of range DA TEMP _ _ _ F 0 F to 140 F 18 C to 60 C DISCHARGE AIR TEMPERATURE after Heating section Displays when Discharge Air sensor is connected and displays measu...

Страница 32: ...2 8 V 2 to 10 Vdc DCV MAXIMUM DAMPER POSITION Displays only if a CO2 sensor is connected Used for Vbz ventilation max cfm setpoint Displays 2 to 10 V if 3 sensors RA OA and MA In AUTO mode dampers con...

Страница 33: ...SET 45 F 35 F to 55 F 2 C to 13 C Incremented by 10 F SUPPLY AIR TEMPERATURE LOW LIMIT Temperature to achieve Freeze Protection close damper and alarm if temperature falls below setup value FREEZE POS...

Страница 34: ...r has failed or become disconnected check wiring then replace sensor if the alarm continues CO2 SENS ERR N A N A CO2 SENSOR ERROR CO2 sensor has failed gone out of range or become disconnected check w...

Страница 35: ...tion settings and checkout menu readings see Table 13 See Tables 14 21 for dry bulb and enthalpy sequence of operation With stage 3 delay STG3 DLY in Advanced setup menu second stage of mechanical coo...

Страница 36: ...v On 0 v Off VENTMIN to VENTMAX Closed On On High 24 v On 24 v On VENTMIN to VENTMAX Closed Yes Off Off High 0 v Off 0 v Off VENTMIN to VENTMAX Closed On Off High 0 v Off 0 v Off VENTMIN to Full Open...

Страница 37: ...O Y2 O OCCUPIED UNOCCUPIED None No Off Off Low 0 v Off 0 v Off MIN POS L Closed On Off Low 24 v On 0 v Off MIN POS L Closed On On High 24 v On 24 v On MIN POS H Closed Yes Off Off Low 0 v Off 0 v Off...

Страница 38: ...y for differential enthalpy The high limit boundary is ES1 when there are no stages of mechanical cooling energized and HL high limit when a compressor stage is energized Table 21 Enthalpy Operation w...

Страница 39: ...ly items that are configured are shown in the Checkout menu NOTE For information about menu navigation and use of the keypad see Interface Overview on page 29 To perform a Checkout test 1 Scroll to th...

Страница 40: ...mpling inlet to the sampling tube on the basepan 2 SPEED INDOOR FAN MOTOR SYSTEM WITH VARI ABLE FREQUENCY DRIVE FACTORY INSTALLED OPTION For details on operating RHH 2 stage cooling units equipped wit...

Страница 41: ...he belt span length by 1 64 For example if the belt span length is 32 inches 32 x 1 64 1 2 inch deflection BELT FORCE DEFLECTION METHOD Check the belt tension with a spring force belt force deflec tio...

Страница 42: ...ners www hvacpartners com TORQUE ALL SHEAVE SET SCREWS TO 110 130 in lbs SET SCREW SET SCREW STRAIGHT EDGE BELT SPAN BELT DEFLECTION FORCE SEE TABLE 1 DEFLECTION BELT SPAN 64 TABLE 1 TABLE 2 BELT CROS...

Страница 43: ...opeller for location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotatin...

Страница 44: ...L2 _____________ L3 _____________ TEMPERATURES Outdoor air Temperature _____________ F DB Dry Bulb Return air Temperature _____________ F DB _____________ F Wb Wet Bulb Cooling Supply Air Temperature...

Отзывы: