ICP Protege DIN Rail Module Network Repeater Скачать руководство пользователя страница 1

PRT-MNR2-

D

IN

 

 

Protege DIN Rail Module Network Repeater 

Quick Start Guide 

 

 

The Protege DIN Rail Module Network Repeater extends the 
network capabilities of the Protege system by allowing modules to 
connect to the system via an Ethernet connection, as well as 
providing optical isolation between up to three branches of the 
module network. 
Using the PRT-MNR2-DIN, you can connect modules via the 
RS-485 network, and the network repeater can be connected to the 
controller using Ethernet. This allows much greater separation and 
ease of wiring than previously possible. In addition, the network 
repeater has three optically isolated RS-485 branches, easing 
power supply requirements. 
When receiving this product, you should find the kit contains the 
items listed below. If you do not have the correct contents, please 
contact your distributor immediately. 

 

Protege DIN Rail Module Network Expander 

 

Protege DIN Rail Module Network Expander Quick Start Guide 

 

3 330R EOL resistors 

For more information on the Protege DIN Rail Module Network 
Repeater and other Integrated Control Technology products please 
visit the ICT website (http://www.ict.co). 

 

1. Power Supply 

 

 

For devices using hardware revision 010, COM1 can only 
be used for supplying power to the network repeater when 
the module is connected via Ethernet. 

 

The network repeater provides the connection of up to three 
optically isolated RS-485 network stubs. To maintain proper 
isolation, each connection requires a separate power supply.   
Power to the network repeater is supplied by the N+ and N- 
terminals on the COM1 port and is also used for the on-board 
electronics and the Ethernet connection.   
It is important that the N+ module power is 12VDC supplied from an 
independent battery backed power supply unit such as the 
PRT-PSU-DIN capable of supplying the required voltage. 

NA

N+

N-

NB

Network communications input
from the Protege Integrated
System Controller or previous
Protege module

 

Standard DC Power Connection 

 

 

Warning:

 

 

The 12V N+ and N- DC power input must be supplied 
from only ONE point. Connections from more than one 
12V supply may cause failure or damage to the 
PRT-MNR2-DIN module. 

 

A 330 Ohm EOL (End of Line) resistor MUST be 
inserted between the NA and NB terminals of the 
module directly connected to the Module Network 
Repeater. 

 

 

End of Line Resistor 

The COM2 and COM3 ports are powered separately and optically 
isolated from each other. 

 

2. Encrypted Module Network 

 

 

For devices using hardware revision 010, you can only use 
COM2 and COM3 to create module network spurs when the 
network repeater is connected via Ethernet. 

 

The network repeater incorporates encrypted RS-485 
communications technology. The isolated communications interface 
offers full galvanic isolation to prevent ground loop noise and cross 
phase ground differential between network devices on the three 
RS-485 ports. 

NA

N+

N-

NB

Network communications input
from the Protege Integrated
System Controller or previous
Protege module

 

Standard Communication Connection 

Always connect the NA and NB terminals of the network repeater to 
the NA and NB terminals of the communication network. The N+ 
and N- must go to a 12V power supply source as shown in the 
following diagram and connected at ONLY one +12V power source. 

NA

N+

N-

NB

NA

N+

N-

NB

Next module 
on network

PRT-MNR2-DIN

AUX power from module or
external power supply

NA

N+

N-

NB

V-

Z1

V+

Z2

Z3

C

Z4

C

12VDC OUT

ZONE INPUT 1-4

 

Network Power Supplied by Network Module 

 

NA

N+

N-

NB

NA

N+

N-

NB

Next module 
on network

PRT-MNR2-DIN

AUX power from module or
external power supply

NA

N+

N-

NB

V-

Z1

V+

Z2

Z3

C

Z4

C

12VDC OUT

ZONE INPUT 1-4