46201200402
12/2015
Specifications are subject to change without notice.
INSTALLATION INSTRUCTIONS
14 SEER Single--Packaged Air Conditioner and
Gas Furnace System with R--410A Refrigerant
Single Phase 2--5 Nominal Tons (Sizes 24--60)
Three Phase 3--5 Nominal Tons (Sizes 36--60)
PGD4 and PGS4 Series E, WPG4 Series B
IMPORTANT
: Effective January 1, 2015, all split system and
packaged air conditioners must be installed pursuant to applicable
regional efficiency standards issued by the Department of Energy.
NOTE
:
Read the entire instruction manual before starting the
installation.
NOTE
:
Installer: Make sure the Owner’s Manual and Service
Instructions are left with the unit after installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . . . . . . . .
INTRODUCTION
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RECEIVING AND INSTALLATION
2--14
. . . . . . . . . . . . . . . . .
Check Equipment
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Identify Unit
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspect Shipment
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Provide Unit Support
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Roof Curb
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Slab Mount
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Field Fabricate Ductwork
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Provide Clearances
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rig and Place Unit
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rigging/Lifting of Unit
3
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connect Condensate Drain
10
. . . . . . . . . . . . . . . . . . . . . . . . . .
Install Flue Hood
11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install Gas Piping
11
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install Duct Connections
12
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuring Units for Downflow (Vertical)
Discharge
12
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Install Electrical Connections
13
. . . . . . . . . . . . . . . . . . . . . . . .
High--Voltage Connections
13
. . . . . . . . . . . . . . . . . . . . . . . .
Special Procedures for 208--V Operation
13
. . . . . . . . . . . . . .
Control Voltage Connections
13
. . . . . . . . . . . . . . . . . . . . . . .
Standard Connection
14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heat Anticipator Setting
14
. . . . . . . . . . . . . . . . . . . . . . . . . .
Transformer Protection
14
. . . . . . . . . . . . . . . . . . . . . . . . . . .
PRE--START--UP
14
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP
15--26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check for Refrigerant Leaks
15
. . . . . . . . . . . . . . . . . . . . . . . . .
Start--Up Heating & Make Adjustments
15
. . . . . . . . . . . . . . . .
Check Heating Control
15
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Check Gas Input
15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjust Gas Input
17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check Burner Flame
17
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Normal Operation
24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Airflow and Temperature Rise
24
. . . . . . . . . . . . . . . . . . . . . .
Heating Sequence of Operation
24
. . . . . . . . . . . . . . . . . . . . .
Limit Switches
24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rollout Switch
24
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start--Up Cooling & Make Adjustments
24
. . . . . . . . . . . . . . . .
Checking Cooling Control Operation
24
. . . . . . . . . . . . . . . .
Checking & Adjusting Refrigerant Charge
25
. . . . . . . . . . . .
Indoor Airflow and Airflow Adjustments
25
. . . . . . . . . . . . .
Cooling Sequence of Operation
26
. . . . . . . . . . . . . . . . . . . . .
MAINTENANCE
53--56
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A09044
Fig. 1 -- Unit PGD4, PGS4, WPG4
(Low NOx Model Available)
Air Filter
53
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indoor Blower and Motor
53
. . . . . . . . . . . . . . . . . . . . . . . . .
Induced Draft (Combustion Air) Blower
54
. . . . . . . . . . . . . .
Flue Gas Passageways
54
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Limit Switch
54
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Burner Ignition
54
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Main Burners
54
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removal of Gas Train
54
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Coil, Indoor Coil, & Condensate Drain Pan
54
. . . .
Outdoor Fan
55
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical Controls and Wiring
55
. . . . . . . . . . . . . . . . . . . . .
Refrigerant Circuit
56
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gas Input
56
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Evaporator Airflow
56
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R--410A Items
56
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING
57
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP CHECKLIST
57
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. consult local
building codes, the current editions of the National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1, and the National Electrical Code
(NEC) NFPA 70.