Installation
iDRY iRDP CT 20-500
23
9.3 Correction
factors
Correction factor for operating pressure modifications:
Inlet air pressure
psig
60
80
100
120
140
160
180
203
barg 4 5.5 7 8 10 11 12 14
Factor (F1)
0.79
0.91
1.00
1.07 1.13 1.18 1.23 1.27
Correction factor for ambient temperature modifications:
Ambient temperature
ºF
80 90 95 100 105 110 115 122
ºC
27
32 35 38 40 43 45 50
Factor (F2)
1.11
1.09
1.06
1.00 0.94 0.87 0.78 0.69
Correction factor for inlet air temperature modifications:
Air temperature
ºF
90 100 110 122 130 140 150 158
ºC
32
38 43 50 55 60 65 70
Factor (F3)
1.16
1.00
0.82
0.68 0.61 0.52 0.45 0.40
Correction factor for DewPoint modifications:
DewPoint
ºF
38
41
45
50
ºC
3
5
7
10
Factor
(F4)
1.00 1.08 1.20 1.36
Calculation of the actual air throughput:
Actual air throughput = air throughput acc. to planning x factor (F1) x factor (F2) x factor (F3) x factor (F4)
Example:
The
iDRY iRDP CT 75
has a planned nominal capacity of 75 scfm (127 m³/h). The highest achievable air
mass under the following operating conditions is:
Air inlet pressure = 120 psig (8 barg)
Ambient temperature = 115°F (45°C)
Air inlet temperature = 122°F (50°C)
Pressure dew point = 50°F (10°C)
Factor (F1) = 1.07
Factor (F2) = 0.78
Factor (F3) = 0.68
Factor (F4) = 1.36
Every function parameter corresponds to a numerical factor which, multiplied by the planned nominal capacity,
determines the following:
Actual air throughput = 75 x 1.07 x 0.78 x 0.68 x 1.36 = 58 scfm (99 m³/h)
58 scfm (99 m³/h)
is the maximum flow rate of the dryer under the aforementioned operating conditions.
Selection of the best suitable model in accordance with the operating conditions:
Air throughput acc. to planning =
Requ. air throughput
Factor (F1) x Factor (F2) x Factor (F3) x Factor (F4)
Example:
The following operating parameters are known:
Required air mass = 100 scfm (170 m
3
/h)
Air inlet pressure = 120 psig (8 barg)
Ambient temperature = 115°F (45°C)
Air inlet temperature = 122°F (50°C)
Pressure dew point = 50°F (10°C)
Factor (F1) = 1.07
Factor (F2) = 0.78
Factor (F3) = 0.68
Factor (F4) = 1.36
To find out the correct dryer version, the required air mass must be divided by the correction factors of the
parameters indicated above:
Air throughput acc. to planning =
100
= 130 scfm (221 m³/h)
1.07 x 0.78 x 0.68 x 1.36
The suitable model for these requirements is
IDRY IRDP CT 150
(with a spec. nominal capacity of
150 scfm [255 m³/h]
).
Содержание iDRY iRDP CT 100
Страница 28: ...Technical data 28 iDRY iRDP CT 20 500 11 Technical data 11 1 Technical data iDRY iRDP CT 20 200 1 1 115 60...
Страница 29: ...Technical data iDRY iRDP CT 20 500 29 11 2 Technical data iDRY iRDP CT 20 500 2 1 230 60...
Страница 30: ...Technical data 30 iDRY iRDP CT 20 500 11 3 Technical data iDRY iRDP CT 200 500 3phase 4 3 460 60...
Страница 38: ...Maintenance troubleshooting spare parts and dismantling 38 iDRY iRDP CT 20 500...
Страница 39: ...Maintenance troubleshooting spare parts and dismantling iDRY iRDP CT 20 500 39...
Страница 42: ...Appendices 42 iDRY iRDP CT 20 500 13 1 2 Dryer dimensions iDRY iRDP CT 75...
Страница 43: ...Appendices iDRY iRDP CT 20 500 43 13 1 3 Dryer dimensions iDRY iRDP CT 100 150...
Страница 44: ...Appendices 44 iDRY iRDP CT 20 500 13 1 4 Dryer dimensions iDRY iRDP CT 200 250...
Страница 45: ...Appendices iDRY iRDP CT 20 500 45 13 1 5 Dryer dimensions iDRY iRDP CT 300 350...
Страница 46: ...Appendices 46 iDRY iRDP CT 20 500 13 1 6 Dryer dimensions iDRY iRDP CT 400 500...
Страница 47: ...Appendices iDRY iRDP CT 20 500 47 13 1 7 Dryer dimensions iDRY iRDP CT 200 250 3phase...
Страница 48: ...Appendices 48 iDRY iRDP CT 20 500 13 1 8 Dryer dimensions iDRY iRDP CT 300 350 3phase...
Страница 49: ...Appendices iDRY iRDP CT 20 500 49 13 1 9 Dryer dimensions iDRY iRDP CT 400 500 3phase...
Страница 51: ...Appendices iDRY iRDP CT 20 500 51 13 2 2 Exploded diagram iDRY iRDP CT 20 30...
Страница 52: ...Appendices 52 iDRY iRDP CT 20 500 13 2 3 Exploded diagram iDRY iRDP CT 50...
Страница 53: ...Appendices iDRY iRDP CT 20 500 53 13 2 4 Exploded diagram iDRY iRDP CT 75...
Страница 54: ...Appendices 54 iDRY iRDP CT 20 500 13 2 5 Exploded diagram iDRY iRDP CT 100...
Страница 55: ...Appendices iDRY iRDP CT 20 500 55 13 2 6 Exploded diagram iDRY iRDP CT 125 150...
Страница 56: ...Appendices 56 iDRY iRDP CT 20 500 13 2 7 Exploded diagram iDRY iRDP CT 200 250...
Страница 57: ...Appendices iDRY iRDP CT 20 500 57 13 2 8 Exploded diagram iDRY iRDP CT 300 350...
Страница 58: ...Appendices 58 iDRY iRDP CT 20 500 13 2 9 Exploded diagram iDRY iRDP CT 400 500...
Страница 59: ...Appendices iDRY iRDP CT 20 500 59 13 2 10 Exploded diagram iDRY iRDP CT 200 250 3phase...
Страница 60: ...Appendices 60 iDRY iRDP CT 20 500 13 2 11 Exploded diagram iDRY iRDP CT 300 350 3phase...
Страница 61: ...Appendices iDRY iRDP CT 20 500 61 13 2 12 Exploded diagram iDRY iRDP CT 400 500 3phase...
Страница 71: ...Appendices iDRY iRDP CT 20 500 71...
Страница 72: ...Independent Compressor Partners LLC Jeffersonville IN 47131 www icompressorpartners com 7425MUM289_EN_2014 09...