12
440 01 4201 03
Specifications subject to change without notice.
Figure 9
Unconverted Factory Configuration as viewed in the Downflow Orientation
Representative drawing only, some models may vary in appearance.
Remove relief tube from relief
port on condensate trap.
Remove pressure switch tube from
pressure switch port.
Remove trap from
collector box.
Loosen clamp on inlet
to vent elbow.
Remove middle and bottom plugs.
DO NOT DISCARD.
Remove tube from
relief port.
A11585A
Downflow Trap Configuration
A11585B
Representative drawing only, some models may vary in appearance.
7
9
Install plugs on
open ports on
collector box.
Connect relief tube to
port on collector box.
Rotate elbow to
desired position and
tighten clamp to
15 lb.
−
in.
Slide tube in stand
−
offs
to adjust length.
Trim excess tube.
Connect pressure switch
tube to port on collector
box.
Attach condensate trap
with screw to collector
box.
Connect relief tube to
relief port on condensate
trap.
Align condensate trap
over middle and bottom
ports of collector box.