ICP F9MES Series Скачать руководство пользователя страница 10

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: F9MES

Specifications  subject to change without notice.

10

440 04 4900 02

Table 3 (CONT.)

Orifice Size and Manifold Pressure (in. w.c.) for Gas Input Rate 

 Single Stage

L12F047B

Adjust Temperature Rise

NOTE

:  Blower door must be installed when taking temperature

rise reading. Leaving blower door off will result in incorrect

temperature measurements, due to possible changes in duct
static pressure and airflow.

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in:

S

Overheating the heat exchangers or condensing

flue gases in heat exchanger areas not designed

for condensate

S

Shortened furnace life

S

Component damage

Temperature rise must be within limits specified on furnace

rating plate. Recommended operation is at midpoint of rise

range or slightly above.

CAUTION

!

Jumper R to W to check gas-heat temperature rise. Do not

exceed temperature rise ranges specified on unit rating plate.
This furnace must operate within the temperature rise ranges

specified on the furnace rating plate. Determine the air

temperature as follows:

1. Place duct thermometers in return and supply ducts as

close to furnace as possible. Be sure thermometers do

not “see” heat exchangers so that radiant heat does not

affect thermometer readings. This is particularly

important with straight

run ducts.

2. When thermometer readings stabilize, subtract return

air

temperature from supply

air temperature to determine

temperature rise.

If the temperature rise is outside this range, check the

following:

1. Gas input rate.
2. Derate for altitude if applicable.
3. Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50

in. w.c. (125

Pa)

4. Adjust temperature rise by adjusting blower speed.

S

Increase blower speed to reduce temperature rise.

S

Decrease blower speed to increase temperature rise.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect 220 vac electrical power before changing speed

tap.

!

WARNING

(Read following caution before changing taps.)

UNIT DAMAGE HAZARD

To avoid operating outside the rise range and avoid

component damage:
Refer to the Air Delivery Tables to determine which airflows

and settings are allowed for proper heating airflow. DO NOT

use the highlighted settings for heating airflow. The

highlighted settings are to be used for Cooling and

Continuous Fan ONLY.

CAUTION

!

Содержание F9MES Series

Страница 1: ...this manual in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used through...

Страница 2: ...d result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which w...

Страница 3: ...d ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 Position Time Off Position Time Off 90 108 120...

Страница 4: ...ates HUM 220vac terminal is only energized when the draft inducer is energized in heating HUM 24vac terminal is only energized on a call for heat W and the LPS is closed Prime Condensate Trap with Wat...

Страница 5: ...ific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain average yearly gas specific gravity from local gas supplier 3 Find inst...

Страница 6: ...r natural gas If required manifold pressure is outside this range change main burner orifices h When correct input is obtained replace cap that conceal gas valve regulator adjustment screw Main burner...

Страница 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 220 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 220 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Страница 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Страница 9: ...CE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 9 Table 3 Orifice Size and Manifold Pressure in w c for Gas Input Rate Single Stage L12...

Страница 10: ...ometers in return and supply ducts as close to furnace as possible Be sure thermometers do not see heat exchangers so that radiant heat does not affect thermometer readings This is particularly import...

Страница 11: ...sub base terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and...

Страница 12: ...1955 1905 1850 1795 1740 1685 1630 1575 Yellow 4 0 1755 1710 1660 1610 1565 1515 1465 1415 1365 1310 Orange 5 3 5 1590 1540 1495 1450 1400 1355 1310 1260 1205 1145 Red 5 3 5 1450 1400 1355 1310 1265...

Страница 13: ...t location accordingly Figure 6 Multipoise Orientations A93041 Electrical Controls and Wiring Pressure Switches Each pressure switch is labeled with the reference location noted as COLLECTOR BOX LPS o...

Страница 14: ...interpret the LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time ex...

Страница 15: ...connections for tightness and controls for proper operation each heating season Service as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust I...

Страница 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Страница 17: ...ld or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and ele...

Страница 18: ...ontrol door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Figure 10 and Figure 11 1 Turn off gas...

Страница 19: ...to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or drain extension pipe 9 Turn gas on at electric switch on...

Страница 20: ...C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate in the unit as a result...

Страница 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 21 Figure 14 Service Label 339462 2 Rev A...

Страница 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 22 440 04 4900 02 339542 2 Rev A...

Страница 23: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 440 04 4900 02 23 Figure 15 Wiring Diagram 339462 2 Rev A...

Страница 24: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace F9MES Specifications subject to change without notice 24 440 04 4900 02 339542 2 Rev A...

Страница 25: ...equence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individua...

Страница 26: ...onent test Does the igniter glow orange white by the end of the 18 second warm up period Unplug igniter harness from control and repeat component test Check for 220V between connector P2 HSI and NEUTR...

Страница 27: ...the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the thermos...

Страница 28: ...injury death or property damage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may...

Отзывы: