ICP DAS WISE User Manual
http://wise.icpdas.com
199
Figure 10-4
:
DI Counter condition setting page
Follow the steps below:
i
Specify the module and the channel from the dropdown list of
the “Module & Channel” section that you are going to include
its value in the IF condition statements.
ii
Set up the expression statement for this counter value. Select an
operator from “=”, “>”, “<”, “>=”, “<=” or “Change”.
iii
Specify the evaluation value. If this DI counter value match the
evaluation criteria, the result of this condition evaluation will be
“true”. WISE provides the following 12 values options; you can
compare them with the DI counter value for condition
evaluation.
Please note: If the statement involves state
transitions: “Change”, user doesn‟t need to set up the evaluation
value. The action will be executed only at the moment when the
state transition occurs.
User-Defined: The “User-Defined” value could be used as
evaluation criteria; input the “User-Defined” value under
the “Value” field.
Internal Register: The “Internal Register” value could be
used as evaluation criteria; select the “Source” and the
number of the Internal Register from the dropdown list.
The “Local” in the “Source” field mean the Internal
Register is from the Host controller (WISE). The
“Remote” in the “Source” field mean the Internal Register
is from the remote WISE controller.