5.1.8
$AAC[delimiter]
Description:
This reads/sets the delimiter for COM 2/3.
Syntax:
$AAC
[chk](CrLf)
Reads the delimiter for COM 2/3 stored in the Flash
$AAC[delimiter]
[chk](CrLf)
Sets the delimiter for COM 2/3
[Request]
Byte 1
Byte 2-3
Byte 4
Byte 5-6
Byte 7-8
Note
$
AA
C
[chk]
(CrLf)
Read
Byte 1
Byte 2-3
Byte 4
Byte 5
Byte 6-7
Byte 8-9
Note
$
AA
C
[delimiter]
[chk]
(CrLf)
Write
$
AA
[delimiter]
[chk]
(CrLf)
Delimiter character
2-character port address in Hex format. The valid range is from 00~FF
Default delimiter is
:
2-character checksum. If the checksum is disabled
no [chk]
End Character
[Response]
Byte 1
Byte 2-3
Byte 4
Byte 5-6
Byte 7-8
Note
!
AA
[delimiter]
[chk]
(CrLf)
Read
Byte 1
Byte 2-3
Byte 4-5
Byte 6-7
Note
!
AA
[chk]
(CrLf)
Valid
?
Invalid
!
?
AA
[chk]
(CrLf)
Delimiter character indicating a valid command
Delimiter character indicating an invalid command
2-character port address in Hex format
2-character checksum. If the checksum is disabled
no [chk]
End Character
If no response
syntax error, communication error ,or address error