The SG-3071 is a voltage input to voltage or current output signal conditioning module. It has 
1000Vdc three-way isolation for input, output and power. And can change the input/output 
range via internal configuration switches.   
 
The SG-3071 has an LED display to show whether the SG-3071 is functioning

 

correctly and 

has two VRs (Zero, Span) to calibrate the input/output range accuracy. 
 
The bandwidth of the SG-3071 is typically 3KHz. It’s easy to mount the SG-3071 on a standard 
DIN rail and can operate in environments with wide temperature range. 
 
                                 

Specifications 
Voltage input: 

ƒ

 Bipolar: ±5V, ±10V 

ƒ

  Unipolar: 0~5V, 0~10V 

ƒ

  Input impedance: 2M

 

ƒ

  Input bandwidth: 3KHz (typical)

-

3dB 

 

Voltage output:

 

ƒ

 Bipolar: ±5V, ±10V 

ƒ

  Drive: 10mA (max.) 

ƒ

  Output impedance: <50

 

 

Current Output: 

ƒ

  Current: 0 ~ 20mA, 4 ~ 20mA 

ƒ

  Current load resistor: 0

500 

 (Source) 

 

General 

ƒ

  Three-way isolation: 1000 Vdc 

ƒ

  Accuracy: ±0.1% of full range (typical) 

ƒ

 Operation temperature range:-25

°

C

75

°

ƒ

  Storage temperature range:-30

°

C

85

°

ƒ

  Operation bandwidth: 3KHz 

ƒ

  Weight: 94 gram 

 

Supply Voltage 

 

ƒ

  Input Range: 10~30Vdc@24Vdc (Typical) 

ƒ

  Consumption: 1.80W (voltage output) 

                 2.30W (current output) 
 
 
                           
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание SG-3071-G

Страница 1: ...1 is typically 3KHz It s easy to mount the SG 3071 on a standard DIN rail and can operate in environments with wide temperature range Specifications Voltage input Bipolar 5V 10V Unipolar 0 5V 0 10V Input impedance 2MΩ Input bandwidth 3KHz typical 3dB Voltage output Bipolar 5V 10V Drive 10mA max Output impedance 50Ω Current Output Current 0 20mA 4 20mA Current load resistor 0 500 Ω Source General T...

Страница 2: ...ange of 10 30Vdc Table 1 shows the switch positions used to configure the input and output range The I O configuration switches are located inside the module And can be accessed by removing the DIN rail bracket covers by sliding them in the direction shown in Figure B Range SW1 Range SW2 SG3071 Input To Output Range 1 2 3 4 5 1 2 3 4 5 10V 10V 10V 5V 5V 5V 5V 10V 0 10V 4 20mA 0 10V 0 20mA 0 5V 4 2...

Страница 3: ...ct pin7 to the 24Vdc connection and pin 10 to GND 2 Connect pin8 and pin 11 to the meter 3 Use wire to connect pins 1 and 2 4 Changing the SW1 and SW2 depends on your input output range Watch the value of the meter and adjust the VR1 ZERO value to the minimum value of this range ...

Страница 4: ...connection and pin 10 to GND 2 Connect pin8 and pin 11 to the meter 3 Connect pins 1 and 2 to input source 4 Changing the SW1 and SW2 depends on your Input Output range Watch the value of the meter and adjust the VR2 SPAN value to the maximum value of this range Block Diagram ...

Страница 5: ...5 Dimensions ...

Отзывы: